Mitsubishi Electric Mr. SLIM SLZ-M FA Serie Manual De Instalación página 19

Ocultar thumbs Ver también para Mr. SLIM SLZ-M FA Serie:
Idiomas disponibles
  • ES

Idiomas disponibles

  • ESPAÑOL, página 95
8. Test run
Step 4 Confi rm the operation of the outdoor unit fan.
The speed of the outdoor unit fan is controlled in order to control the performance of the unit. Depending on the ambient air, the fan will rotate at a slow speed and will keep
rotating at that speed unless the performance is insuffi cient. Therefore, the outdoor wind may cause the fan to stop rotating or to rotate in the opposite direction, but this is
not a problem.
Step 5 Stop the test run.
1 Press the [ON/OFF] button to stop the test run. (The Test run menu will appear.)
Note: If an error is displayed on the remote controller, see the table below.
LCD
Description of malfunction
P1
Intake sensor error
P2
Pipe sensor error (liquid pipe)
Drain fl oat switch connector disconnected
P4
(CN4F)
P5
Drain overfl ow protection operation
Freezing/overheating protection
P6
operation
P8
Pipe temperature error
See the table below for the details of the LED display (LED 1, 2, and 3) on the indoor controller board.
LED 1 (microcomputer power supply)
LED 2 (remote controller power supply)
LED 3 (indoor/outdoor unit communication)
45
7
Fig. 8-5
8.3. Self-check
■ Refer to the installation manual that comes with each remote controller for details.
• Refer to the following tables for details on the check codes. (Wireless remote controller)
[Output pattern A]
Beeper sounds
Beep
OPERATION
INDICATOR
lamp blinking
Off
pattern
Approx. 2.5 sec.
Self-check
starts
(Start signal
Number of blinks/beeps in pattern indicates the check
received)
code in the following table (i.e., n=5 for "P5")
[Output pattern B]
Beeper sounds
Beep
OPERATION
INDICATOR
lamp blinking
Off
pattern
Approx. 2.5 sec.
Self-check
starts
(Start signal
received)
LCD
P9
PA
Pb
PL
FB
U*, F*
(* indicates an
alphanumeric
character
excluding FB.)
Indicates whether control power is supplied. Make sure that this LED is always lit.
Indicates whether power is supplied to the wired remote controller. The LED is lit only for the indoor unit that is con-
nected to the outdoor unit that has an address of 0.
Indicates whether the indoor and outdoor units are communicating. Make sure that this LED is always blinking.
8
6
23
Beep
Beep
Beep
Beep
1
st
2
nd
3
rd
th
n
On
On
On
On
0.5 sec.
0.5 sec.
0.5 sec.
0.5 sec.
Beep
Beep
st
nd
1
2
On
On
On
Approx. 3 sec.
0.5 sec.
0.5 sec.
Number of blinks/beeps in pattern indicates the check
code in the following table (i.e., n=5 for "U2")
Description of malfunction
Pipe sensor error (dual-wall pipe)
Leakage error (refrigerant system)
Indoor unit fan motor error
Refrigerant circuit abnormal
Indoor controller board error
Outdoor unit malfunction
Refer to the wiring diagram for the
outdoor unit.
8.2.2. Using the wireless remote controller
Turn on the power to the unit at least 12 hours before the test run.
1
Press the
button for 5 seconds. (Fig. 8-5)
2
(Perform this operation when the remote controller display is turned off.)
Press the
button.
3
[TEST] and the current operation mode are displayed. (Fig. 8-5)
A
Press the
button to activate cool mode, then check whether cool air is
4
blown out from the unit.
Press the
button to activate heat mode, then check whether warm air is
5
blown out from the unit.
Press the
button and check whether the fan speed changes.
6
Press the
button and check whether the auto vane operates properly.
7
Press the
button to stop the test run.
8
(After two hours, a signal will be sent to stop the test run.)
Note:
• Point the remote controller towards the indoor unit receiver while following
steps
to
.
3
8
• It is not possible to perform the test run in FAN, DRY, or AUTO mode.
Beep
Beep
st
nd
1
2
· · · Repeated
Off
On
On
Approx. 2.5 sec.
0.5 sec.
0.5 sec.
Number of blinks/beeps in pattern indicates
the check code in the following table
Beep
Beep
rd
th
3
n
On
On
Off
0.5 sec.
0.5 sec.
Approx. 2.5 sec.
LCD
Description of malfunction
Communication error between the
E0 – E5
remote controller and the indoor unit
Communication error between the
E6 – EF
indoor unit and the outdoor unit
Beep
Beep
st
nd
1
2
· · · Repeated
On
On
On
Approx. 3 sec.
0.5 sec.
0.5 sec.
Number of blinks/beeps in pattern indicates
the check code in the following table
en
17
loading

Este manual también es adecuado para:

Mr. slim slz-m15fa2