A
COMBUSTION AIR FLOW ADJUSTMENT (HIGH-LOW FLAME)
2
1
C
2) - Increase or decrease the air flow rate through the adjusting ring nut 1 (Clockwise to increase, coun-
terclockwise to decrease).
3) - Tighten clamping ring nut 2.
4) - Switch manually from Low flame to High flame and check the combustion values.
All burners are factory tested at 380V - 60Hz 3-phase for motors, and 220V - 60Hz single phase with
neutral for auxiliary equipments. Should it be necessary to power the burner with 220V - 60Hz,
modify the connections on motor and the terminal board as shown in the picture. Protect the burner
supply line with suitable fuses and/or other safety devices as required by the local regulations on the
matter.
FIRING HEAD SETTING
MAX
MIN
Air flow rate adjustment in Low flame running:
1) - Start the burner (checking that the air damper is
partially open).
2) - Loosen clamping screw D.
3) - Turn air damper C until obtaining a correct combu-
stion (checked with a combustion gas analysis set).
+
–
4) - Tighten clamping screw D.
Air flow rate adjustment in High flame running:
WARNING: due to the presence of oil under pressure in
the hydraulic jack when the burner is working in High
flame condition, the air flow rate adjustment is to be
made with the use of an adjusting ring nut 1 with the
burner running in Low flame condition. The combu-
D
stion checks are to be done once the burner is turned to
High flame condition again.
1) - Loosen clamping ring nut 2