CONFIGURATION ACCORDING TO THE INCOMING ELECTRICITY
SUPPLY
To configure the equipment
according to the incoming
electricity supply, use the dial
on the rear of the front panel
or via the mobile/web app.
This adjustment is essential for
the correct operation of the
load modulator.
For app or web programming
to take effect, the rotating
selector must be in the "NO
LIMIT." position.
If the TMC100 transformer is not installed because modulation is not nec-
essary, it is advisable to limit the load current with the rotary selector to
the maximum power that we want to allocate to the charger.
In the "NO LIMIT" position, the charging power would not be limited and
could go to the maximum that the charger can give (7.4 kW in single
phase/22 kW in three-phase).
In installations where the TMC-100 is not required, as another meter
(SPL, VIARIS SOLAR or others) is used, the position of the rotary must be
in "NO LIMIT."
Single-phase
Current
power
NO LIMIT.
NO LIMIT.
10 A
2,3 kW
13 A
3 kW
15 A
3,45 kW
18 A
4,14 kW
20 A
4,6 kW
23 A
5,3 kW
25 A
5,75 kW
Three-phase
power
NO LIMIT.
6,928 kW
9 kW
10,392 kW
12,42 kW
13,856 kW
15,9 kW
17,321 kW
66
Single-phase
Current
power
28 A
6,44 kW
30 A
6,9 kW
35 A
8,05 kW
40 A
9,2 kW
45 A
10,35 kW
50 A
11,5 kW
55 A
12,65 kW
63 A
14,49 kW
Three-phase
power
19,32 kW
20,785 kW
24,249 kW
27,713 kW
31,177 kW
34,641 kW
37,95 kW
43,648 kW