Salicru SPS.ADVANCE RT2 Manual De Usuario página 64

Idiomas disponibles
  • ES

Idiomas disponibles

Models.
Available power ratings (VA / W).
Connectors with protection for ADSL/fax/modem.
Connector for external EPO installation
Slot for optional cards.
Optional cards (to insert in slot).
Monitoring software.
Audible noise at 1 m in battery mode.
Working temperature.
Storage temperature with batteries.
Storage temperature without batteries.
Working altitude.
Relative humidity.
Protection rating.
Standard UPS module.
Dimensions (mm)
Depth × Width ×
UPS module B1.
Height.
Optional battery module.
Standard UPS module.
Weight (kg).
UPS module B1.
Optional battery module.
Safety.
Electromagnetic compatibility (EMC).
Operation.
Marking.
Quality system.
(1)
80 % power reduction for 208 V devices.
Tab. 17. General technical specifications.
10.1. GLOSSARY.
AC.-
Alternating current is electric current in which the
magnitude and direction vary cyclically. The waveform of the
most commonly used alternating current is that of a sine wave,
since this achieves a more efficient transmission of energy. In
certain applications, however, other periodic waveforms are
used, such as triangular or square.
Bypass.-
Manual or automatic, this is the physical connection
between the input of an electrical device and its output.
DC.-
Direct current is the continuous flow of electrons through
a conductor between two points with different potential.
Unlike AC, in DC, electrical loads always circulate in the same
direction from the point of greatest potential to the lowest.
Although DC is commonly identified as a continuous current
(for example, that supplied by a battery), any current that
always maintains the same polarity is continuous.
DSP.-
Digital signal processor. A DSP is a processor or
microprocessor-based system that has a set of instructions,
hardware and optimised software for applications that require
numerical operations at very high speed. Because of this, it
is especially useful for the processing and representation of
analogue signals in real time: in a system that works in this
way (real time) samples are usually received from an analogue/
digital converter (ADC).
Power factor.-
defined as the ratio between active power, P, and apparent
power, S, or as the cosine of the angle formed by the current
and voltage factors, designated in this case as cos f , where f is
the value of the angle.
64
800 / 720
< 45 dB
410 x 438 x 88 (2 U)
410 x 438 x 88 (2 U)
12.9
14.4
The power factor, PF, of an AC circuit is
ADVANCE RT2.
1,100 / 990
1,500 / 1,350
RJ45 connectors, 1 input and 1 output.
Interface to relays (AS400), SNMP, remote Internet or intranet management, MODBUS
ViewPower (free download).
0.. +40 ºC
–20.. +50 ºC
–20.. +70 ºC
2,400 masl (power degradation up to 5,000 m)
10.. 95 % non-condensing.
410 x 438 x 88 (2 U)
13.4
9
16.2
EN-IEC 62040-1
EN-IEC 62040-2 (C2)
EN-IEC 62040-3
ISO 9001 and ISO 140001
GND.-
This stands for GROUND or EARTH and, as the name
indicates, refers to the potential of the surface of the Earth.
EMI filter.-
electromagnetic interference (EMI), which is the disturbance
that occurs in a radio receiver or in any other electrical circuit
caused by electromagnetic radiation coming from an external
source. Electromagnetic interference is also known as radio
frequency interference (RFI). This disturbance can interrupt,
degrade or limit the performance of the circuit
IGBT.-
An insulated gate bipolar transistor is a semiconductor
device that is generally used as a controlled switch in power
electronics circuits. This device possesses the characteristics
of the gate signals of field effect transistors with the capacity
for high current and low saturation voltage of the bipolar
transistor, combining an isolated FET gate for input and control
and a bipolar transistor as a single switch in a single device.
The IGBT's excitation circuit is similar to that of the MOSFET,
while the conducting characteristics are similar to those of the
BJT.
Interface.-
an interface (electronics) is the port (physical circuit) through
which signals are sent or received from one system or
subsystem to another
kVA.-
A volt-ampere is the unit used for apparent power in
electrical current. In DC, it is practically equal to real power
but, in AC, it can differ from this depending on the power
factor.
2,000 / 1,800
Yes
Yes
< 50 dB
IP20
510 x 438 x 88 (2 U)
510 x 438 x 88 (2 U)
19.5
21.5
11
24.7
28.4
CE
Filter capable of significantly reducing
In electronics, telecommunications and hardware,
3,000 / 2,700
630 x 438 x 88 (2 U)
630 x 438 x 88 (2 U)
29.3
11.9
40.6
SALICRU