Salicru SPS.ADVANCE RT2 Manual De Usuario página 63

Idiomas disponibles
  • ES

Idiomas disponibles

9. ANNEXES.
10. GENERAL TECHNICAL SPECIFICATIONS.
Models.
Available power ratings (VA / W).
Technology.
Input.
Input type.
Number of cables.
Rated voltage.
Input voltage range.
Input frequency range.
Permissible power factor loads.
Cold start (from batteries).
Inverter.
Technology.
Waveform.
Power factor.
Rated voltage.
Output voltage accuracy (battery mode).
Total harmonic distortion (THDv), with linear load.
Frequency.
Transfer time, line mode to battery mode (normal
mode).
Performance at full load, in normal mode with
battery 100% charged.
Performance at full load, in battery mode.
Overload in line mode
Overload in battery mode.
Crest factor.
Batteries (AGM sealed 3 - 5 years life).
Element voltage.
Capacity.
Number of batteries in device connected in series
/ group voltage.
Number of accumulators in battery module
connected in series x no. packs in parallel / group
voltage.
Low battery voltage.
Blocking voltage for group end of backup.
Internal battery charger.
Group floating voltage.
Maximum charge current.
Recharge time.
Optional internal battery charger (B1).
Maximum charge current.
Other functions.
Cold start.
Emergency power off (EPO).
IEC output sockets programmable at disconnection,
for non-critical loads.
General.
IEC input connectors.
IEC output connectors.
Communication ports.
Potential-free contacts.
USER MANUAL
800 / 720
1,100 / 990
Line-interactive with sine-wave output.
3 cables - Phase R (L) + Neutral (N) and earth.
208 / 220 / 230 / 240 V AC
45.. 55 / 55.. 65 Hz ± 0.2 Hz; auto-detectable.
Yes, by default with frequency of 50 Hz.
208 / 220 / 230 / 240 V AC
With mains present, synchronised to rated input (45.. 55 / 55.. 65 Hz).
With mains absent -backup mode- 50 / 60 ±0.1 Hz.
> 89 %
7 Ah
9 Ah
2 / 24 V DC
2 x 2 / 24 V DC
22.4 V DC
19.2 V DC
27.2 V DC
8 hours to 90%
10 A IEC 14 connector.
8 x 10 A IEC 13 (4 for critical loads + 4 for non-critical loads programmable at disconnection) +
1 x 16 A IEC 19 (only in 3 kVA model)
2 (1 x RS232 -DB9- and 1 x USB, mutually exclusive).
Yes, using optocouplers in the same connector as the RS232.
ADVANCE RT2.
1,500 / 1,350
2,000 / 1,800
Single-phase.
(1)
176.. 288 V AC
0.9
PWM
Pure sine wave.
0.9
(1)
, selectable
± 1.5 %
< 2 %
2..6 ms
> 97 %
> 90 %
> 91 %
103.. 120 %: 5 min
> 120.. 150 %: 10 s
> 150 %: 1 s
103.. 120 %: 1 min
> 120.. 150 %: 10 s
> 150 %: 0.5 s
3:1
12 V DC
7 Ah
4 / 48 V DC
4 x 2 / 48 V DC
44.8 V DC
38.4 V DC
54.4 V DC
1.5 A
4 hours to 90%
3 hours to 90%
8 A
Yes
Yes
Yes
16 A IEC 20 connector.
SPS.ADVANCE RT2 UNINTERRUPTIBLE POWER SUPPLY (UPS)
3,000 / 2,700
> 92 %
9 Ah
6 / 72 V DC
6 x 2 / 72 V DC
67.2 V DC
57.6 V DC
81.6 V DC
4 hours to 90%
63
loading