List of parameters
ES
Min. heating power
Max. heating power
TR
Heating switch-on timer
RO
Heating power delivery ramp
Delay in heating switch-on for Room Ther-
mostat or Remote Friend Control demands
IE
Domestic circuit thermostat
Circulating pump operation
Domestic circuit heat exchanger preheating
Gas
Relay 1 functioning
Relay 2 functioning
Relay 3 functioning
After selecting the parameter to be modified confirm the selection by tem-
porarily turning the main switch to Reset until the LED relevant to the
parameter goes off then release it.
After confirmation the second level is entered for setting the value of the
parameter selected. The value is indicated by slow flashing of one of the
LEDs between 2 and 11, at the same time as LED 1 flashing. The value is
selected by turning the heating temperature knob (14).
After selecting the parameter to be modified confirm the selection by tem-
porarily turning the main switch to Reset until the LED relevant to the
parameter goes off then release it.
Programming mode is quitted if no operation is carried out for 30 seconds,
or if the main switch is turned to Off from the "parameter setting" level.
For the LED-parameter association, see the following tables:
Heating power. The boiler is produced and set to rated power during heat-
ing. It is also equipped with electronic modulation that adapts boiler power
to actual room heating requirements. Therefore the boiler operates normally
in a variable gas pressure range between the minimum and maximum heat-
ing power according to the system thermal load.
N.B: The selection of "Min. heating power" and "Max. heating power",
in the presence of a heating demand, allows boiler lighting and feeding of
the modulator with a current equal to the value of the respective parameter
selected.
Eolo Maior 32kW: adjust min. heat output for room heating keeping to
the values given in the table on page 119 relevant to the boiler variable
heat output.
Min. heating power
(continuous variation)
0% Imax. (standard setting)
7% Imax.
14% Imax.
21% Imax.
28% Imax.
35% Imax.
42% Imax.
114
49% Imax.
56% Imax.
LED flashing (fast)
LED 2
63% Imax.
LED 3
Max. heating power
LED 4
(continuous variation)
LED 5
0% Imax.
LED 6
11% Imax.
LED 7
22% Imax.
LED 8
33% Imax.
LED 9
44% Imax.
LED 10
55% Imax.
LED 11 and 2
66% Imax.
LEDs 11, 2 and 3
77% Imax.
LEDs 11, 2, 3 and 4
88% Imax.
100% Imax. (standard setting)
Permanent timing reduction. The boiler is equipped with an electronic
timer that prevents too frequent igniting of the burner in heating phase. The
boiler comes standard with the timer adjusted to 180 seconds.
Heating switch-on timer (continuous
variation)
30 seconds
55 seconds
80 seconds
105 seconds
130 seconds
155 seconds
180 seconds (standard setting)
205 seconds
230 seconds
255 seconds
LED flashing (slow)
LED 2
LED 3
LED 4
LED 5
LED 6
LED 7
LED 8
LED 9
LED 10
LED 11
LED flashing (slow)
LED 2
LED 3
LED 4
LED 5
LED 6
LED 7
LED 8
LED 9
LED 10
LED 11
LED flashing (slow)
LED 2
LED 3
LED 4
LED 5
LED 6
LED 7
LED 8
LED 9
LED 10
LED 11