Manual
P / Pref
dp 1
dp 2
Fig. 50: Example characteristic curve without hysteresis
10.2.3.1 Parameters for P(U)
Country-
Me-
Display/
spec. Set-
nu
Setting
tings
level
Modo de funciona-
3
1
2
4
4
miento
Off | On
Potencia de referencia
Potencia actual | Po-
tencia nominal
Tensión evaluada
1
2
3
4
4
Maximum phase vol-
tage | Positive sequen-
ce voltage
Hysteresenmodus
Off | On
Deactivation gradient
0 – 65,534 [% /
min] /
min] /
Deactivation time
0 – 60,000,000
[ms] /
Gradiente salida ascen-
diente & Gradiente sa-
lida decreciente
1 – 65,534 [%/Min] /
65,534 [%/min] /
1
Kaco blueplanet 29.0TL3
Voltage
Action in this menu/meaning
F Activate the control process.
Off: Deactivates dynamic grid support using dynamic reactive current.
Dynamic grid support remains active on account of immunity to interfe-
rence.
Specifies the power reference for the characteristic curve. 100 % here
corresponds to the nominal power or the actual power at the time the
function was activated, the time when the voltage passes the configu-
red node.
F Select the voltage to be rated.
Defines which voltage in a three-phase system is to be evaluated.
Off: In Non-Hysteresis mode, the active power is increase immediately
in cases of falling voltage.
On: In Hysteresis mode the power is not increased in case of falling vol-
tage.
If the available power is above the actual output at the time of deactiva-
tion, the power increase back to the maximum power is limited. The li-
mitation is implemented by an absolute power limitation that increases
100 [% /
with a continuous gradient up to the maximum power. The actual po-
1
wer of the inverter may vary freely below this limit due to a possible
fluctuation in the available power or the target value, but at no time in-
creases above the absolute power limit.
Only evaluated with activated hysteresis mode: Monitoring time during
which the voltage must remain below the lowest configured node befo-
re the function is deactivated.
100 [ms]
1
Specifies the dynamic response on changing the active power for power
increase. With a voltage change, the active power is changed with the
specified gradient.
The gradient is overlaid with the settling time.
Specifies the dynamic response on changing the active power for power
decrease. With a voltage change, the active power is changed with the
specified gradient.
The gradient is overlaid with the settling time.
Specifications | 10
P / Pref
dp 1
dp 2
dp 3
Fig. 51: Example characteristic curve with hysteresis and a
deactivation threshold below the activation threshold
Voltage
Página 65