Kaco blueplanet 29.0TL3 S Manual De Instrucciones página 47

Idiomas disponibles

Idiomas disponibles

Manual
Country-
Me-
Display/
spec. Set-
nu
Setting
tings
level
Potencia Lock-Out
1
2
3
4
4
0-100 [% S
[% S
] /
n
Hora Lock-In
1
2
4
4
3
0 – 60 [s]
Hora Lock-Out
1
2
4
4
3
0 – 60 [s]
Tiempo muerto
4
1
2
3
4
0-10 000 [ms]
Rise Outg. grad. & Fall.
1
2
3
4
4
Outg. grad.
ascendente | des-
cendente
1 %-60000 %/min
1 %-60000 %/min
Cos-Phi Q1 mín. - Cos-
1
2
3
4
4
Phi Q4 mín.
0.3 – 1 ind/cap /
1 /
0.001
Modo de prioridad
1
2
4
4
3
Q priority | P priority
Curva activa
1
2
3
4
4
1 - 4
Restablecer curva
1
2
3
4
4
Núm. de pu. de apoyo
1
2
3
4
4
2 - 10
Kaco blueplanet 29.0TL3
Configuration and operation | 9
Action in this menu/meaning
F Set the active power as % of rated power below which control is de-
activated.
] /
20
n
1
F Set the length of time that the active power must remain below the
lock-in power level before control is activated.
F Set the length of time that the active power must remain below the
lock-out power level before control is deactivated.
Si, con la regulación activa, la tensión pasa de una sección de la curva
característica donde Q=0 a una sección de la curva característica donde
Q≠0, el ajuste de la potencia reactiva se retrasará en el tiempo muerto
establecido. Una vez transcurrido el tiempo muerto, el circuito de regu-
lación volverá a ser instantáneo; el tiempo de ataque establecido deter-
minará el comportamiento de ataque.
F Ajuste la modificación máxima de potencia reactiva %S
cambiar a funcionamiento con sobreexcitación.
F Ajuste la modificación máxima de potencia reactiva %S
cambiar a funcionamiento con infraexcitación.
AVISO: In the event of a significant voltage deviation, the ma-
ximum reactive power adjustment range can be limited by a
minimum cos φ in order to prevent an excessive reactive po-
wer supply and, as a result, a significant reduction in the maxi-
mum active power that can be fed in.
F Enter the minimum cos ϕ factor for quadrants 1 and 4.
F Set priority for reactive power – Q or active power – P.
AVISO: When it comes to P priority, the reactive power adjust-
ment range is limited subject to the active power that is cu-
rrently available and fed in.
F Select active curve.
AVISO: Up to 4 characteristic curves can be configured inde-
pendently and one of them can be activated for regulation
each time.
F Reset active curve to the default setting.
AVISO: The maximum number of configurable nodes depends
on the selected grid type.
F Specify the number of nodes for the Q(U) characteristic curve.
/min al
lím.
/min al
lím.
Página 47