Power Requirements; Power Supply - SFS isoweld 3000m Manual De Usuario

Ocultar thumbs Ver también para isoweld 3000m:
Tabla de contenido
Idiomas disponibles
  • ES

Idiomas disponibles

  • ESPAÑOL, página 107
Power requirements Part 1
General
The points below describe the power requirements for the use of the
isoweld
induction machine. These notes are recommendations. Each job site
®
and its power situation is individual and therefore no performance guarantee
can be given.
In addition to the recommendations stated in this document, the local safety
and electrical regulations applicable in the country of use must be observed.
Consultation of a qualified electrician is advisable.
Electrical safety
Connect the machine to a socket with a protective earth conductor. Any
breakage/disconnection of the protective conductor inside or outside
the tool is potentially dangerous! Use only extension cables with an
earth conductor!
When the tool is used on building sites, the use of an RCD switch is a
mandatory requirement for personal protection.

Power supply

Stable power is essential for problem-free operation of the induction machine.
A minimum of
- 20 amps per electrical circuit required for countries with 110 volts /
120 volts nominal voltage
- 10 amps per electrical circuit required for countries with 230 volts
nominal voltage
Maximum one induction machine per circuit, with a recommendation not to
use other devices on the same circuit as the isoweld
Off-load voltage shall not exceed:
- 160 volts for countries with 110 volts / 120 volts nominal voltage
- 240 volts for countries with 230 volts nominal voltage
On-load voltage at the point of utilisation at the machine terminals, with the
machine running, must be higher than:
- 110 volts for countries with 110 volts / 120 volts nominal voltage
- 200 volts for countries with 230 volts nominal voltage
It is preferable for the induction machine to have its own dedicated power
supply so as to avoid power surges from other equipment, e.g. drill machines.
Generator
Use a minimum 5000 watt generator
Requirements volts and amps see above
With ground fault circuit interrupter (GFCI)
Grounding / earthing required
Transformer
Necessary for use in countries with a nominal voltage of 110 volts if the volta-
ge at the point of utilisation, with the machine running, falls below 110 volts.
The functionality of the system is only ensured if the transformer provided by
SFS is used.
42
3000, isoweld
®
®
3000m.
Tabla de contenido
loading

Este manual también es adecuado para:

Isoweld 300015225771345351

Tabla de contenido