9.
To activate the temperature compensation press the
10.
Upon completion of this process the display will indicate the
measured resistance value and other test information.
Measured resistance
R=
Resistance
compensated
Rc: 9.843m
Analog current
indication
01:22
Elapsed time
11.
The unit of measured resistance shall be expressed in Ω (ohms),
mΩ (mili-ohms) or µΩ (micro-ohms).
12.
This information can be saved in the machine's internal memory
during and / or after the test simply by pressing the save key
.
13.
To finish the test press the red stop key
product with the power switch
button
14.
Finally, after all measurements have been completed, switch the
device off using the on / off switch
Caution: Never connect or disconnect the test leads with the equipment
in operation. If you have to make any changes to the connection, it must
be done with the equipment turned off.
9.876m
Ω
Ω
[
ίίίίίί
]
.
15
Measured temperature
:25.8 C
:25.0 C
8.5 A
82mV
Measured voltage
. Do not turn off the
without pressing the stop
.
button.
Reference
temperature
Test current