Operation; Phase Rotation Direction; Instrument Front; Faceplate - Chauvin Arnoux AEMC 6612 Manual De Usuario

Medidor de rotación de fases
Tabla de contenido
Idiomas disponibles

Idiomas disponibles

3.1 PHASE ROTATION DIRECTION

On a three-phase electrical network:
1. Connect the three leads to the instrument, matching the markings.
2. Connect the three alligator clips to the 3 phases of the network to be tested.
3. The display lights up, indicating that the instrument is in operation.
4. When the three phase indicators (L1, L2, and L3) are lit, the clockwise (or
counterclockwise) rotation arrow indicates the direction of phase rotation.
WARNING: The wrong direction of rotation may be displayed
if a lead is connected in error to the neutral conductor. Refer
to the instrument's back label (see Figure 2 in § 3.3.1) for a
summary of the various display possibilities.

3.2 INSTRUMENT FRONT

3.2.1 Faceplate

8

3. OPERATION

850 V
CAT III 1000 V
CAT IV 600 V
PHASE ROTATION
MODEL 6612
Figure 1
Phase Rotation Meter Model 6612 - User Manual

Capítulos

Tabla de contenido
loading

Este manual también es adecuado para:

2121.91

Tabla de contenido