2.1. IMPORTANT RECOMMENDATION

„ Failure to observe the procedure described risk causing a dangerously high voltage for the operator
on the clamp's output and causing damage to the clamp.
„ Do not clamp onto a conductor before connecting the clamp to the relevant measuring instrument. Also,
do not disconnect the measuring instrument while the clamp is still gripping the cable.
„ Ensure that you keep the gap perfectly clean.
„ Do not «click» the jaws together so as to avoid damaging the jaw faces.

2.2. METHOD OF OPERATION

Proceed as follows:
1. Connect the cable from B102 clamp's outlet to the multimeter paying careful attention to
the polarity.
2. Select the more appropriate rating on the clamp (P1, P2) and the appropriate size of receiver
for the output signal, which must be adequately insulated.
Position on image
P1
P2
Figure 2: Reminder of the selector switch's positions.
3. Open the jaws and clamp either the conductor whose current is to be measured or the
various conductors for the differential current measurements.
Ensure that the clamp is correctly closed (no foreign body in the gap).
Carefully observe the direction of the arrow, if the application requires this (source at the base of
the arrow, receiver at the tip) mainly for mains system or power analysers
4. Determine the current in the conductor by applying the appropriate readout coefficient
to measured value according to the rating selected on the multimeter and the clamp's
sensitivity.

2. USE

Selector switch position
400 A or 1 mV/A
4 A or 1000 mV/A
17
Readout
400 mV for 400 A or 1 mV per A
1 mV for 1 mA or 1000 mV per A