Mitsubishi Electric TRANE NTXUKS06A112A Serie Manual De Instalación página 2

Ocultar thumbs Ver también para TRANE NTXUKS06A112A Serie:
Idiomas disponibles

Idiomas disponibles

CONTENTS
1. BEFORE INSTALLATION ..................... 1
2. INDOOR UNIT INSTALLATION ............ 4
3. FLARING WORK AND PIPE
CONNECTION ..................................... 7
4. TEST RUN............................................ 9
5. GRILLE (OPTION) INSTALLATION ..... 9
1. BEFORE INSTALLATION
1-1. THE FOLLOWING SHOULD ALWAYS BE OBSERVED FOR SAFETY
• Be sure to read "THE FOLLOWING SHOULD ALWAYS BE OBSERVED FOR SAFETY" before installing the air conditioner.
• Be sure to observe the warnings and cautions specified here as they include important items related to safety.
• After reading this manual, be sure to keep it together with the OPERATING INSTRUCTIONS for future reference.
• Please report to your supply authority or obtain their consent before connecting this equipment to the power supply system.
I Do not install the unit by yourself (user).
Incomplete installation could cause fire or electric shock,
injury due to the unit falling, or leakage of water. Consult
the dealer from whom you purchased the unit or a quali-
fied installer.
I Perform the installation securely referring to the
installation manual.
Incomplete installation could cause fire or electric shock,
injury due to the unit falling, or leakage of water.
I When installing the unit, use appropriate protec-
tive equipment and tools for safety.
Failure to do so could cause injury.
I Install the unit securely in a place which can bear
the weight of the unit.
If the installation location cannot bear the weight of the
unit, the unit could fall causing injury.
I Electrical work should be performed by a quali-
fied, experienced electrician, according to the
installation manual. Be sure to use an exclusive
circuit. Do not connect other electrical appliances
to the circuit.
If the capacity of the power circuit is insufficient or there
is incomplete electrical work, it could result in a fire or
an electric shock.
I Ground the unit correctly.
Do not connect the ground to a gas pipe, water pipe,
lightning rod or telephone ground. Defective grounding
could cause electric shock.
I Do not damage the wires by applying excessive
pressure with parts or screws.
Damaged wires could cause fire or electric shock.
I Be sure to cut off the main power in case of set-
ting up the indoor P.C. board or wiring works.
Failure to do so could cause electric shock.
I Use the specified wires to connect the indoor and
outdoor units securely and attach the wires firmly
to the terminal block connecting sections so the
stress of the wires is not applied to the sections.
Do not extend the wires, or use intermediate con-
nection.
Incomplete connecting and securing could cause fire.
I Do not install the unit in a place where flammable
gas may leak.
If gas leaks and accumulates in the area around the
unit, it could cause an explosion.
I Do not use intermediate connection of the power
cord or the extension cord and do not connect many
devices to one AC outlet.
It could cause a fire or an electric shock due to defective
contact, defective insulation, exceeding the permissible
current, etc.
I Be sure to use the parts provided or specified
parts for the installation work.
The use of defective parts could cause an injury or
leakage of water due to a fire, an electric shock, the
unit falling, etc.
EN-1
6. PUMPING DOWN .............................. 10
7. CONNECTING AN INTERFACE (OPTION)
TO THE AIR CONDITIONER .................. 10
This installation manual describes only
for the indoor unit. Refer to the MXZ type
manual for outdoor unit set up.
WARNING
I When plugging the power supply plug into the
outlet, make sure that there is no dust, clogging,
or loose parts in both the outlet and the plug.
Make sure that the power supply plug is pushed
completely into the outlet.
If there is dust, clogging, or loose parts on the power
supply plug or the outlet, it could cause electric shock or
fire. If loose parts are found on the power supply plug,
replace it.
I Attach the disp cover to the indoor unit and the
service panel to the outdoor unit securely.
If the disp cover of the indoor unit and/or the service
panel of the outdoor unit are not attached securely, it
could result in a fire or an electric shock due to dust,
water, etc.
I When installing, relocating, or servicing the unit,
make sure that no substance other than the
specified refrigerant (R410A) enters the refriger-
ant circuit.
Any presence of foreign substance such as air can
cause abnormal pressure rise and may result in explo-
sion or injury. The use of any refrigerant other than
that specified for the system will cause mechanical
failure, system malfunction, or unit breakdown. In the
worst case, this could lead to a serious impediment to
securing product safety.
I Do not alter the unit.
It may cause fire, electric shock, injury or water leakage.
I Do not discharge the refrigerant into the atmos-
phere. Check that the refrigerant gas does not
leak after installation has been completed. If
refrigerant leaks during installation, ventilate the
room.
If refrigerant comes in contact with a fire, harmful gas
could be generated.
If refrigerant gas leaks indoors, and comes into contact
with the flame of a fan heater, space heater, stove, etc.,
harmful gases will be generated.
I Use appropriate tools and piping materials for
installation.
The pressure of R410A is 1.6 times more than R22.
Not using appropriate tools or materials and incomplete
installation could cause the pipes to burst or injury.
I When the refrigeration circuit has a leak, do not
execute pump down with the compressor. When
pumping down the refrigerant, stop the compres-
sor before disconnecting the refrigerant pipes.
If the refrigerant pipes are disconnected while the
compressor is running and the stop valve is open, air
could be drawn in and the pressure in the refrigeration
cycle could become abnormally high. This could cause
the pipes to burst or injury.
I Fix the connecting cable at the prescribed posi-
tion securely.
Incorrect installation may cause electric shock,
fire, and/or malfunction.
Required Tools for Installation
Phillips screwdriver
Level
Scale
Utility knife or scissors
2-15/16 in. (75 mm) hole saw
Torque wrench
Wrench (or spanner)
(Could lead to death, serious injury, etc.)
I When installing the unit, securely connect the
refrigerant pipes before starting the compressor.
If the compressor is started before the refrigerant pipes
are connected and when the stop valve is open, air could
be drawn in and the pressure in the refrigeration cycle
could become abnormally high. This could cause the
pipes to burst or injury.
I Fasten a flare nut with a torque wrench as speci-
fied in this manual.
If fastened too tight, a flare nut may break after a long
period and cause refrigerant leakage.
I The unit shall be installed in accordance with
national wiring regulations.
I Do not use means to accelerate the defrosting
process or to clean, other than those recommended
by the manufacturer.
I The appliance shall be stored in a room without
continuously operating ignition sources (for exam-
ple: open flames, an operating gas appliance or an
operating electric heater).
I Do not pierce or burn.
I Be aware that refrigerants may not contain an odour.
I Pipe-work shall be protected from physical damage.
I The installation of pipe-work shall be kept to a
minimum.
I Keep any required ventilation openings clear of
obstruction.
I Keep gas-burning appliances, electric heaters, and
other fire sources (ignition sources) away from the
location where installation, repair, and other air
conditioner work will be performed.
I Exercise caution when using any auxiliary heat
source and follow all third party manufacturer
instructions and safety guidelines for installation
and usage.
Any auxiliary heat source connected to this unit via the
CN24 connection must have an independent tempera-
ture control mechanism. Failure to install and maintain
such temperature control mechanism may void the
warranty for this unit.
Mitsubishi Electric shall not bear any warranty obligation
or other liability for any damage or loss in connection
with such third party auxiliary heaters.
FOR INSTALLER
Flare tool for R410A
Gauge manifold for R410A
Vacuum pump for R410A
Charge hose for R410A
Pipe cutter with reamer
Water bottle
0.9 to 1.0 L water
loading