ACCESS TO MENUS
Press the OK key
OK
BFT
Control unit software version
LIBRA1. 0
No. total manoeuvres
OK
0000
(in thousands)
0000
No. manoeuvres since latest
00
maintenance(in thousands)
No. radio control devices
memorised
PARAM
+/-
END
- +
LOGIC.
+/-
END
- +
FOLLOWING MENUS
FIG. B
16 - LIBRA-UL-R - Ver. 06
8 888
[ 00 ]
Preset value
Parameter increment/reduction
/ON
/OFF
or ON/OFF commutation
Press OK key (Enter/confirm)
OK
- +
Menu scrolling
(+ = preceding - = following)
+/-
OK
TCA
- +
m1 torque
- +
m2 torque
- +
m1 t slow
- +
m2 t slow
- +
open delay time
- +
cls delay time
- +
m1 fast time
- +
m2 fast time
- +
slov speed
- +
zone
+/-
[oFF]
OK
OK
TCA
- +
[off]
3 step
OK
- +
[off]
ibl open
OK
- +
[off]
fast cls
OK
- +
[off]
OK
photoc. open
- +
[off]
OK
TEST PHOT
- +
[off]
OK
i Mot ON
- +
[off]
OK
BLOC persist
- +
[off]
OK
start - close
- +
[off]
OK
fixed code
- +
[on]
OK
radio prog
- +
[off]
OK
master
Fig. A
+
OK
[0010]
OK
OK
[0050]
OK
OK
[0050]
OK
OK
[0045]
OK
OK
[0045]
OK
OK
[001. 0 ]
OK
OK
[001. 0 ]
OK
OK
[015. 0 ]
OK
OK
[015. 0 ]
OK
OK
[0000]
OK
OK
[0000]
OK
OK
ON
OK
PRG
OFF
ON
OK
PRG
OFF
ON
OK
PRG
OFF
ON
OK
PRG
OFF
ON
OK
PRG
OFF
ON
OK
PRG
OFF
ON
OK
PRG
OFF
ON
OK
PRG
OFF
ON
OK
PRG
OFF
ON
OK
PRG
OFF
ON
OK
PRG
OFF
ON
OK
PRG
OFF
LEGENDA
+/-
Simultaneously press the + and - keys.
Simultaneous pressure of the + and – keys
allows you to exit the active menu and return
to the preceding menu; if this takes place at
the main menu level, programming is exited
and the display switched off.
The modifications made are only confirmed if
the OK key is subsequently pressed.
Message: Programming in progress
PRG
Message: KO! (value or function error)
Message: "Wait" (enter value or function)
PRG
PRG
PRG
PRG
PRG
PRG
PRG
PRG
PRG
PRG
PRG
PARAMETER MENU
TCA (automatic closing time)
value expressed in seconds
(default 10=10s, min 3=3s, max 60=60s)
Motor 1 torque value expressed in %
(default 50%, min 1%, max 99%)
Motor 2 torque value expressed in %
(default 50%, min 1%, max 99%)
Motor 1 torque slow-down
value expressed in %
(default 45%, min 1%, max 99%)
Motor 2 torque slow-down
value expressed in %
(default 45%, min 1%, max 99%)
Opening delay time
value expressed in tenths of a second
(default 10=1s, min 10=1s, max 100=10s)
Closing delay Time
value expressed in tenths of a second
(default 10=1s, min 10=1s, max 10=10s)
Motor 1 Normal speed time
value expressed in seconds
(default 15=15s, min 1=1s, max 30=30s)
Motor 2 Normal speed time
value expressed in seconds
(default 15=15s, min 1=1s, max 30=30s)
Slow-down speed
0= Slow-down disabled
1= 50% of normal speed
2= 33% of normal speed
3= 25% of normal speed
Zone numerical value
(default 0, min 0, max 127)