INVERTER BOX INTERNAL TEMPERATURE
Displays the box internal Temperature.
CAPACITOR TEMPERATURE
Displays the power capacitors temperature
INPUT ACTIVATION STATUS
Displays the input signal activation Status
1= enabled input
OUTPUT ACTIVATION STATUS
Displays the output relay activation Status
1= enabled input
STATUS RS 485 (SLAVE connection)
Displays the status of the inverter SLAVE connected to the
inverter MASTER.
XX-XX = no SLAVE inverter connected
S1-XX = inverter SLAVE1 connected
XX-S2 = inverter SLAVE2 connected
S1-S2 = inverter SLAVE1 e SLAVE2 connected
Back to the parameter SYSTEM PRESSURE
tasto
+
ENTER
+
ENTER
Display the serial number and the firmware version
tasto
START / STOP
+
- Do not run pumps dry
- Before starting the pump, make the filling of all pumps
- In the pressure units, the filling is for single pump by turning off all other pumps
- When the pump is completely filled with water, bring in TEST mode (manual operation) and prime
the pump by opening the discharge valve gradually
- When the pump is primed, stop the manual mode by pressing STOP and switch to automatic
mode by pressing START.
0= input not enabled
0= input not enabled
Set pressure quick adjustment
istruzione
To increase the SET PRESSURE by 0,1 bar
To decrease the SET PRESSURE by 0,1 bar
istruzione
DGFIT out of service
Display the SERIAL NUMBER and the
FIRMARE version
PRIMING AND STARTING UP
41
° C
Ti 30
° C
Tc 40
In 0
Ou 0
S1-S2
bar
P 3.5
display
P 3.5
P 3.6
P 3.5
P 3.4
display
OFF
SN – DGF 1501 ...