In TEST mode you start and adjust the pump manually
-
- Enter the TEST mode by pressing the SET key for 3 sec. and scroll to TEST (see instruction
below)
During the test, you can view all the operating parameters (see below)
-
Key
x 3 sec.
SET
X 3
START
X 10
STOP
- During automatic operation you can display the working parameters (see below)
Key
Instruction
SYSTEM PRESSURE
none
Displays the system pressure
OPERATING FREQUENCY
Displays the motor revolution Frequency.
ABSORBED CURRENT
Displays the motor absorbed current.
INPUT VOLTAGE
Displays the inverter input Voltage (mains power voltage).
Power factor (COSFI):
Shows the instantaneous value of the power factor.
POWER MODULE TEMPERATURE
Displays the inverter's electronic module temperature.
Sets the full scale for pressure
sensor.
10-16-25-40 bar
Press the ENTER key until the display shows "OK"; Base and Advanced
menu will be factory restored.
Instruction
Enter the MAIN MENU
Scroll to TEST menu
Start the pump (at 30 Hz)
Display the operating frequency
Increase the operating frequency by steps of 1
Hz

Display the operating parameters

Stop the pump and exit TEST mode
DISPLAY THE OPERATING PARAMETERS
description

TEST

40
u.m. Default Min
Bar
16
10
display
BASIC
TEST
P 1.5 (example)
F 30
F 40 (example)
A 4.5 (example)
OFF
display
P 3.5
F 45
A 6.5
V 400
PF .85
Tm 50
Max
Step
40
-
u.m.
bar
Hz
A
V
° C