Mitsubishi Electric Mr.SLIM PUZ-ZM71VHA Manual De Instalación página 16

Idiomas disponibles
  • ES

Idiomas disponibles

  • ESPAÑOL, página 59
8. Special functions
A
X
F
SW1
B
A Circuit diagram example (low noise mode)
B On-site arrangement
C External input adapter (PAC-SC36NA-E)
X: Relay
A
X
Y
F
SW2
SW3
B
A Circuit diagram example (Demand function)
B On-site arrangement
en
X, Y: Relay
8.3. Refrigerant collecting (pump down)
Perform the following procedures to collect the refrigerant when moving the indoor
unit or the outdoor unit.
1 Supply power (circuit breaker).
* When power is supplied, make sure that "CENTRALLY CONTROLLED" is not
displayed on the remote controller. If "CENTRALLY CONTROLLED" is dis-
played, the refrigerant collecting (pump down) cannot be completed normally.
* Start-up of the indoor-outdoor communication takes about 3 minutes after the
power (circuit breaker) is turned on. Start the pump-down operation 3 to 4
minutes after the power (circuit breaker) is turned ON.
2 After the liquid stop valve is closed, set the SWP switch on the control board of
the outdoor unit to ON. The compressor (outdoor unit) and ventilators (indoor and
outdoor units) start operating and refrigerant collecting operation begins. LED1
and LED2 on the control board of the outdoor unit are lit.
* Only set the SWP switch (push-button type) to ON if the unit is stopped. However, even
if the unit is stopped and the SWP switch is set to ON less than 3 minutes after the
compressor stops, the refrigerant collecting operation cannot be performed. Wait until
compressor has been stopped for 3 minutes and then set the SWP switch to ON again.
9. System control (Fig. 9-1)
E SW 1 - 3 ~ 6
ON
OFF
3
4
ON
F SW 1 - 3 ~ 6
OFF
3
4
G SW 1 - 3 ~ 6
ON
OFF
3
4
A E
TB1
TB1
TB4
TB4
B
B
2
TB5
TB5
1
C
D
10. Specifications
Outdoor model
Power supply (V / Phase / Hz)
Dimensions (H × W × D)
Cooling
Sound level *1
Heating
*1 Measured under rated operation frequency.
14
C
D
Orange
CNDM
1
Brown
X
Red
3
E
D Outdoor unit control board
E Max. 10 m
F Power supply for relay
C
D
CNDM
Orange
1
X
Brown
Red
3
Y
E
C External input adapter (PAC-SC36NA-E)
D Outdoor unit control board
E Max. 10 m
F Power supply for relay
A Outdoor unit
B Indoor unit
C Master remote controller
5
6
D Subordinate remote controller
E Standard 1:1 (Refrigerant address = 00)
F Simultaneous twin (Refrigerant address = 01)
G Simultaneous triple (Refrigerant address = 02)
5
6
5
6
A
F
A
G
TB1
TB4
TB4
TB4
B
B
B
2
TB5
1
Fig. 9-1
ZM71
230 / Single / 50
mm
943 × 950 × 330(+25)
47
dB(A)
49
8.1. Low noise mode (on-site modification) (Fig. 8-1)
By performing the following modification, operation noise of the outdoor unit can be
reduced by about 3-4 dB.
The low noise mode will be activated when a commercially available timer or the
Fig. 8-1
contact input of an ON/OFF switch is added to the CNDM connector (option) on the
control board of the outdoor unit.
• The ability varies according to the outdoor temperature and conditions, etc.
1 Complete the circuit as shown when using the external input adapter
(PAC-SC36NA-E). (Option)
2 SW7-1 (Outdoor unit control board): OFF
3 SW1 ON: Low noise mode
SW1 OFF: Normal operation
8.2. Demand function (on-site modification) (Fig. 8-2)
By performing the following modification, energy consumption can be reduced to
0–100% of the normal consumption.
The demand function will be activated when a commercially available timer or the
contact input of an ON/OFF switch is added to the CNDM connector (option) on the
Fig. 8-2
control board of the outdoor unit.
1 Complete the circuit as shown when using the external input adapter
(PAC-SC36NA-E). (Option)
2 By setting SW7-1 on the control board of the outdoor unit, the energy consump-
tion (compared to the normal consumption) can be limited as shown below.
Demand
function
3 Because the unit automatically stops in about 2 to 3 minutes when the refrigerant
collecting operation is completed (LED1 off, LED2 lit), be sure to quickly close the
gas stop valve. If LED1 is lit and LED2 is off and the outdoor unit is stopped, refrig-
erant collection is not properly performed. Open the liquid stop valve completely,
and then repeat step 2 after 3 minutes have passed.
* If the refrigerant collecting operation has been completed normally (LED1 off,
LED2 lit), the unit will remain stopped until the power supply is turned off.
4 Turn off the power supply (circuit breaker).
* Note that when the extension piping is very long with large refrigerant amount,
it may not be possible to perform a pump-down operation. When performing
the pump-down operation, make sure that the low pressure is lowered to near
0 MPa (gauge).
Warning:
When pumping down the refrigerant, stop the compressor before disconnect-
ing the refrigerant pipes. The compressor may burst if air etc. get into it.
* Set the refrigerant address using the DIP switch of the outdoor unit.
1 Wiring from the Remote Control
This wire is connected to TB5 (terminal board for remote controller) of the indoor
unit (non-polar).
2 When a Different Refrigerant System Grouping is Used.
Up to 16 refrigerant systems can be controlled as one group using the slim MA remote controller.
Note:
In single refrigerant system (twin/triple), there is no need of wiring 2.
SW1
Function table
<SW1>
TB4
ON
OFF
B
1 2 3 4 5 6
SW7-1
SW2
SW3
OFF
OFF
ON
OFF
ON
ON
ON
OFF
ON
Function
1
Compulsory de-
frosting
SW1
2
Error history clear
function
3
Refrigerant system
settings
4
address setting
5
6
Energy consumption
100%
75%
50%
0% (Stop)
Operation according to
switch setting
ON
OFF
Start
Normal
Clear
Normal
Settings for outdoor unit
addresses 0 to 15
loading