Lamborghini Caloreclima EM 16-E Manual Para La Instalacion Y El Mantenimento página 41

Ocultar thumbs Ver también para EM 16-E:
Idiomas disponibles

Idiomas disponibles

CALIBRATION OF AIR PRESSURE SWITCH
The air pressure switch places the burner in safety mode or shuts it down should there be a
drop in combustion air pressure. It will be calibrated at a pressure below 1st stage rated-flow
on-burner air pressure, checking that CO values do not exceed 10,000 p.p.m.
CALIBRATION OF MINIMUM GAS PRESSURE SWITCH
The minimum gas pressure switch serves to prevent the burner from being started up or to
shut it down if the gas pressure falls below the minimum required level. This setting should
be 40% lower than the gas pressure obtained with the burner operating at maximum delivery.
PRESSURE SWITCH
Type:
LGW 3 A2
GW 50 A5
GW 150 A5
Remove the cover and
adjust dial A
Air pressure switch
Model
EM 16-E
EM 16/L-E
EM 26-E
Pressure
connector
Setting range
DUNGS type
LGW 3 A2
LGW 3 A2
Gas pressure switch
mbars
DUNGS type
GW 50 A5
0,4 - 3
GW 150 A5
0,4 - 3
41
Setting range
mbars
5 - 50
5 - 150
UK
loading

Este manual también es adecuado para:

Em 26-eEm 16/l-e