7. HYDRA-Gauge with switch contacts
7.4 Specifications
Range of operating voltage
Residual ripple
No-lead current
Switching current
Leakage current
Function of switching element
Type of output
Voltage drop (with I max.)
Reverse polarity protection
Anti-inductive protection
Oscillator frequency
EMC per
Ambient conditions and temperature in accordance with measuring instrument
Installation

7.5 Adjusting the set pointers

The adjustment of the set points is
achieved using the adjustment lock
in the window with the aid of the
adjustment key (included in delivery).
The set pointers for the limit switches are freely adjustable over the full scale range. For
reasons of switching accuracy and service life of the mechanical measuring systems, the
switch points should be between 10 % and 90 % of the measuring range.
WIKA operating instructions HYDRA-Gauge
Electronic contact model 830 E
DC 10 ... 30 V
max. 10 %
≤ 10 mA
≤ 100 mA
≤ 100 mA
Normally open
PNP transistor
≤ 0.7 V
conditional U
(the output 3 or 4 switch must never be set
B
directly to minus)
1 kV, 0.1 ms, 1 kΩ
approx. 1000 kHz
EN 60947-5-2
installed directly in the measuring instrument at the factory,
maximum 2 switch contacts per measuring instrument