6. Commissioning, operation
Index
Object
(decimal)
name
67
OU1
EN
68
SP2 or
FH2
69
RP2 or
FL2
70
OU2
72
Unit
73
HIGH
74
LOW
75
DS1
76
DR1
77
DS2
78
DR2
26
Format
Access
8 Bit
R/W
Enumeration
16 Bit
R/W
unsigned
16 Bit
R/W
unsigned
8 Bit
R/W
Enumeration
8 Bit
R/W
Enumeration
16 Bit
R
unsigned
16 Bit
R
unsigned
16 Bit
R/W
unsigned
16 Bit
R/W
unsigned
16 Bit
R/W
unsigned
16 Bit
R/W
unsigned
WIKA operating instructions pressure switch model PSA-31 for sanitary applications
Value range
0 = HNO = hysteresis function,
normally open
1 = HNC = hysteresis function,
normally closed
2 = FNO = window function,
normally open
3 = FNC = window function,
normally closed
1,040 ... 9,000
1,000 ... 8,960
0 = HNO = hysteresis function,
normally open
1 = HNC = hysteresis function,
normally closed
2 = FNO = window function,
normally open
3 = FNC = window function,
normally closed
0 = bar
1 = Mpa
2 = kPa
3 = psi
4 = kg/cm²
0 ... 10,000
0 ... 10,000
0 ... 50,000 (0 ... 50 s)
0 ... 50,000 (0 ... 50 s)
0 ... 50,000 (0 ... 50 s)
0 ... 50,000 (0 ... 50 s)
Factory
Remarks
setting
0
Switching function
switching output 1
9,000
Switch point/window
High switching output 2
8,200
Reset point/window Low
switching output 2
0
Switching function
switching output 2
Order-related
Unit change. MBA and
MBE must be read again
after writing.
-
Max. value memory
-
Min. value memory
0
Switch delay time switch
point 1
0
Switch delay time reset
point 1
0
Switch delay time switch
point 2
0
Switch delay time reset
point 2