Having trouble
Do I need to jumper the 'To Furnace'
contacts over to the 'To Thermostat'
contacts?
I am seeing the system short-cycle
when heating with the furnace.
How do I reset the system?
Specifications are subject to change without notice.
PAA-A18, 24, 30, 36, 42AA1/BA1/CA1
Here is the solution (Unit is operating normally)
No. Please follow the installation instructions described in
the PAA unit installation manual.
TH1 may be mounted too close to the furnace and you
are seeing the heat from the furnace cause an over-temp
condition. Move it further down the return air plenum, away
from the furnace.
1. Power down the furnace and outdoor unit and wait 3
minutes.
2. Power up the outdoor unit.
3. Power up the furnace.