Note:
The maximum line length between the module and the
end-of-line resistor must not exceed 10 m.
Before fixing the module into place, feed connecting cables
through the cable entry hole at the rear of the module housing.
The module may be connected with a NO configuration or a
NC configuration. See Figure 2 and Figure 3.
Addressing
Each module must be assigned an address from 1 to 128. Use
the rotary dial marked 0 to 12 to set the tens and hundreds part
of the address, and the rotary dial marked 0 to 9 for the
remaining digits. See Figure 4 for sample address settings.
Note:
To overcome the mechanical effects of shipping and
storage, we recommend that you first rotate each dial counter-
clockwise (to the 0 position), and then clockwise (to the dial's
maximum position) before setting the required address.
To change the address of a module that is operational:
1.
Disconnect the module from the loop.
2.
Change the address on the module using the rotary dials.
3.
Connect the module to the loop.
4.
Configure the device at its new address, and then remove
the old device address at the panel.
Maintenance
Basic maintenance consists of a yearly inspection. Do not
modify internal wiring or circuitry.
Specifications
Operating voltage
Voltage modulation
Current consumption
Standby
Active
End-of-line resistor
Response time [1]
Environmental
IP rating
Operating environment
Operating temperature
Storage temperature
Relative humidity
Weight
Dimensions
[1] This value depends on panel programming.
2 / 20
17 to 28 VDC
4 to 10 VDC
<205 µA
<270 µA
150 kΩ, 5%, 1/4 W
<1 s
Indoor use only
IP40
−10 to +55°C
−20 to +60ºC
10 to 95% noncondensing
144 g
125 × 90 × 35 mm
Regulatory information
This section provides a summary on the declared performance
according to the Construction Products Regulation
(EU) 305/2011 and Delegated Regulations (EU) 157/2014 and
(EU) 574/2014.
For detailed information, see the product Declaration of
Performance (available at firesecurityproducts.com).
EU compliance
Certification body
0370
Declaration of
10-5106-360-1001-01
Performance number
17
Year of first CE
marking
Product identification
IU2050NC
Intended use
See the product Declaration of Performance
Declared performance
See the product Declaration of Performance
Manufacturer
United Technologies Safety System Co. Ltd.
80, Changjiang East Road,
QETDZ, Qinhuangdao,
Hebei Province, China 066004
Authorized EU manufacturing representative:
UTC Fire & Security B.V.
Kelvinstraat 7, 6003 DH Weert, Netherlands
2012/19/EU (WEEE directive): Products
marked with this symbol cannot be disposed
of as unsorted municipal waste in the
European Union. For proper recycling, return
this product to your local supplier upon the
purchase of equivalent new equipment, or
dispose of it at designated collection points.
For more information see:
http://www.recyclethis.info.
Contact information
For contact information, visit firesecurityproducts.com.
Product warnings and disclaimers
THESE PRODUCTS ARE INTENDED FOR SALE TO, AND
INSTALLATION BY, AN EXPERIENCED SECURITY
PROFESSIONAL. UTC FIRE & SECURITY CANNOT
PROVIDE ANY ASSURANCE THAT ANY PERSON OR
ENTITY BUYING ITS PRODUCTS, INCLUDING ANY
"AUTHORIZED DEALER", IS PROPERLY TRAINED OR
EXPERIENCED TO CORRECTLY INSTALL SECURITY
RELATED PRODUCTS.
For more information on warranty disclaimers and product
safety information, please check
https://firesecurityproducts.com/productwarning/ or scan the
following code:
P/N 10-5106-501-50NC-02 • 02MAR18
loading