Product Specifications
Table 7. Protection Characteristics (Continued)
Short Circuit (Utility Mode)
Short Circuit (Battery Mode)
Table 8. Battery Characteristics
Battery Type
Recharge time
Backup Time (Full Load)
Table 9. Alarm
On Battery
Battery Low
Overload
Table 10. Environment
Ambient Operation
Audible Noise
Vibration
Shock
Table 11. Weights and Dimensions
Net Weight, lb. (kg)
H x W x D, in. (cm)
Eaton Din Rail UPS Advanced User Guide 9340AC—Rev A
18
In the event of dead short on the outputs of the UPS, input fuse will break. Once the
fuse opens, UPS operates in Battery Mode and engages Battery Mode Short Circuit
Protection until OSCP is removed.
Retry until the short circuit is removed or battery defect.
DIN500AC
Sealed, maintenance-free, lead acid batteries.
4 min.
DIN500AC
Slow beeping every 3 seconds
Rapid beeping every second
Continuous beeping sound
DIN500AC
0–95% humidity, non-condensing. up to 122 °F at 6600 ft. (50°C at 2000 m)
<40 dBA (1 m from surface)
Operating - IEC60068-2-6, Sine Wave: 10 Hz to 500 Hz @ 2g, displacement of 0.35
mm, 60 minutes per axis for Y direction
Non-operating - IEC60068-2-6, Random : 5 Hz to 500 Hz @ 2g (RMS), 20 minutes per
Operating - IEC60068-2-27, Half Sine-Wave: 10G for a duration of 11ms, shock for 1
Non-operating - IEC60068-2-27, Half Sine-Wave : 30G for duration of 11ms, 1 shock
DIN500AC
5.2 x 12.28 x 5.5 (13.16 x 31.2 x 13.93)
DIN850AC
8 hours
1.5 min.
DIN850AC
DIN850AC
axis for X, Y, Z
direction (Y axis)
for all 3 axes
DIN850AC
11.60 (5.2)