JR-D / JR20-D
1, 2, 3 and 4 control modes (for counter mode 'Cont' and Setpoint 2 only)
MODE 1: INDEPENDIENT
Relays will be activated when main counter
reaches their respective Setpoint values. They
will be deactivated when the necessary
conditions are met depending on how output
is configured, 'pulse' or 'latched'. Outputs are
respectively
shown
overlapped
in
right
diagrams as
or
.
MODE 2: STOP
Relay 1 activates when the main counter
reaches its respective Setpoint value and
Relay 2 stops it when Setpoint 2 is reached.
Main counter remains stopped until a RESET
is done. Relays will be deactivated when
display goes down below their respective
Setpoint value.
MODE 3: RESET
Relay 1 activates at its Setpoint value. When
main counter reaches Setpoint 2, a main
counter RESET is done. Relay 2 ouput is pulse
type and remains active for the programmed
time. Relay 1 will be deactivated if display
goes down below Setpoint 1 value.
MODE 4: CLEAR
Relay 1 activates at its Setpoint value. When
main counter reaches Setpoint 2, relay 2
activates and relay 1 is deactivated (if it was
activated). Relay 2 output is latched type.
Main counter goes on until a RESET sets
display to programmed OFFSET value. Relay
2 will be deactivated if display goes below
Setpoint 2.
* In all cases, the behaviour of OUT1 and OUT2 outputs relays, and consequently of the main counter, changes
depending on defined OFFSET level.
Pulse output "PuLS" (Counter mode only 'Cont') (
)
Relay activates when its Setpoint is reached by display and deactivates after a period of time. This activation time
is a parameter which can be programmed between 0.1s and 9.9s.
Latched output "LAtC" (Counter mode only 'Cont') (
)
Relay activates when its Setpoint is reached by display and remains activated until a RESET makes display go
below that Setpoint.