Carrier WTC-B-207 Instrucciones De Instalación página 15

Idiomas disponibles
  • ES

Idiomas disponibles

  • ESPAÑOL, página 62
10. WTC LEDs operation
LONWORKS
Rx/Tx LEDs (Rx – Receiving / Tx – Transmitting)
Rx LED not blinking
Tx LED not blinking
Status LED – Normal Operation
One fast blink
Fast blink continuous
• • • • •
(150ms On, 150ms Off, continuous)
The Status LED is always ON
Status LED blink patterns – Repeats every 2 seconds (highest priority shown first)
Long Blink Continuous
(1s On, 1s Off, continuous)
Long Long Long blink
(800ms On, 300ms Off, 800ms On, 300ms
Off, 800ms On)
Long Short Short Short blink
• • •
(800ms On, 300ms Off, 150ms On, 300ms
Off, 150ms On, 300ms Off, 150ms On)
Fast blink 12x
• • • • • • • • • • • •
(80ms On, 80ms Off, 12x)
BACNET
Rx/Tx LEDs (Rx – Receiving / Tx – Transmitting)
Rx LED not blinking
Tx LED not blinking
Status LED – Normal Operation
One fast blink
Fast blink continuous:
• • • • •
(150ms On, 150ms Off, continuous)
The Status LED is always ON
Status LED blink patterns – Repeats every 2 seconds (highest priority shown first)
Long Long Long blink
(800ms On, 300ms Off, 800ms On,
300ms Off, 800ms On)
Short Long blink
(150ms On, 300ms Off)
Order No.: 10083, 10.2016 - Supersedes order No.: 10083, 08.2015.
Data is not being received from the LonWorks data bus.
Data is not being transmitted onto the LonWorks data bus.
Initialization: The device is starting up.
Firmware upgrade in progress. Controller operation is
temporarily unavailable. The new firmware is being loaded into
memory. This takes a few seconds. Do not interrupt power to
the device during this time.
The controller is operating normally.
The controller is not configured.
Action: Commission the controller.
The controller is offline.
Action: Set the controller Online.
The controller is in bypass mode.
Action: Set the controller Online.
Wink. The wink function is used to identify a device.
Data is not being received from the BACnet MS/TP data bus.
Data is not being transmitted onto the BACnet MS/TP data bus.
Initialization: The device is starting up.
Firmware upgrade in progress. Controller operation is
temporarily unavailable. The new firmware is being loaded into
memory. This takes a few seconds. Do not interrupt power to
the device during this time.
The controller is operating normally.
The device has not received a BACnet token, and therefore
cannot communicate on the network: Verify that the control-
ler's MAC Address is unique on the BACnet MS/TP Data
Bus. Make sure the controller's BAUD rate is the same as the
BACnet MS/TP Data Bus' BAUD rate. Verify that the Max
Master is set high enough to include this controller's MAC
Address (see also NCI documentation).
Invalid MAC address: The device's MAC address is set to
zero (0) or is set to an address higher than the Max Master
(see also NCI documentation).
15
loading

Este manual también es adecuado para:

Wtc-b-307Wtc-l-207Wtc-l-307