Premium EPS-120-5192 Manual De Operación página 7

Ocultar thumbs Ver también para EPS-120-5192:
Idiomas disponibles

Idiomas disponibles

3. DESCRIPTION OF THE EPS-120-5192 AND EPS-200-5193 SYSTEMS
The EPS-120-5192 and EPS-200-5193 are 48V rectifiers-battery chargers that are able to manage the charging
of lead batteries, with capacities ranging from 1Ah to 15Ah and 10Ah to 20Ah respectively.
The total power that the EPS-120-5192 can deliver is 120W on a continuous basis, and 180W for 10 seconds
every minute. The input voltage is 230VAC.
The total power that the EPS-200-5193 can deliver is 200W on a continuous basis, and 400W for 10 seconds
every minute. The input voltage is 230VAC.
The charger-rectifier architecture that is used has the battery connected directly to the output, as can be seen
in the following figure:
Phas
Neutral
Groun
This equipment's function is that of an uninterruptible power supply system, and its mission is to maintain
power to the loads at all times. To do so, it must:
-Provide an uninterruptible power supply at its output that is within the specified range.
-Protect itself in normal operating situations (power-up, intermittent overloads, etc.), as well as
abnormal ones (short circuits and continuous overloads at its output, etc.).
-Carry out appropriate treatment of the batteries required for its operation:
-Try to maximize the life of the batteries and minimize their charging time.
-Implement protections against inappropriate operations that could damage them (deep
discharge and adjustment of floating voltage with temperature).
www.premiumpsu.com
Powering Your Challenge
Figure 1. View EPS-120-5192 and EPS-200-5193 modules
AC / DC
Control V-I
10kV isolation
Figure 2. Diagram of blocks.
BATTERY
Serie EPS
Manual de Operación
+48Vcc
0V
MA-5192A-1
20-10-2021
7 / 84
loading

Productos relacionados para Premium EPS-120-5192

Este manual también es adecuado para:

Eps-200-5193