Premium EPS-120-5192 Manual De Operación página 11

Ocultar thumbs Ver también para EPS-120-5192:
Idiomas disponibles

Idiomas disponibles

J1
Figure 5. EPS-120-5192 and EPS-200-5193 dimensions and connections
5.2
ELECTRICAL BEHAVIOUR:
The following units have been defined in order to specify the dielectric strength:
UNIT
SIGNAL
G1
AC input
G2
Alarms
G3
Temperature sensor + 48V output + Battery + NC
G4
Ethernet Port
G5
Ground
The dielectric strength between units is as follows:
Testing poles
Pole-1
G1
G2 + G3 + G4 + G5
G2
G1 + G3 + G4 + G5
G1 + G5
G3
(G2 + G4 together without connecting
to G5)
G4
G1 + G2 + G3 + G5
5.3
PROTECTIONS
The mains input is protected by a fuse that is dimensioned for extreme cases in which the device could break
internally and require specialized technical servicing.
The device protections are as follows:
Mains overvoltage protection with varistors.
Secondary overvoltage protection.
Output overload and short-circuit protection with current limiting.
The battery has different degrees of protection:
Electronic charging current limitation.
Short-circuit protection with a self-rearming fuse.
www.premiumpsu.com
Powering Your Challenge
Pole-2
Lightning
Dielectric strength
impulse
50Hz 1 minute
1.2/50µs
± 20 kV
10 kVac
± 2 kV
1 kVac
± 5 kV
2 kVac
± 2 kV
1 kVac
Serie EPS
Manual de Operación
J2
J4 J3
ETH
Isolation with
impulse
± 5 kV
± 2 kV
± 5 kV
± 2 kV
MA-5192A-1
20-10-2021
11 / 84