4. The flashing cursor should be displayed
highlighting the 'i-PCB' Alarm (Warning) Input.
The Default setting for this parameter is +V=!. If
the 'i-PCB' Alarm input detects a voltage between
12-250VAC/DC, an alarm (Warning) condition is
generated. The values for this parameter are:
+V=! for an Alarm (Warning) condition is
o
generated if the 'ir-PCB' Alarm input
detects a voltage between 12-250Vac/dc
(default)
0V=! for an Alarm (Warning) condition is
o
generated if the 'ir-PCB' Alarm input
detects no voltage.
5. Scroll up (+)
to change the value for the Alarm condition
required for your application. Press the enter
button to confirm your selection. You
should be returned to the C02 home screen and
'ir-PCB' should appear next to the 01-01
parameter.
IRV-PCB SETUP
1. Scroll up (+)
to change the value to IRV-PCB. Press the enter
button to confirm your selection.
2. The flashing cursor should be displayed
highlighting the Compressor Start Sequence
Time. The Default setting for this parameter is
10 Sec. This is the time required to start the
motor and then load the compressor. The values
for this parameter are "0" to "60".
3. Scroll up (+)
to change the value to the time required. Press
the enter
button to confirm your selection.
4. The flashing cursor should be displayed
highlighting the 'i-PCB' Alarm (Warning) Input.
The Default setting for this parameter is +V=!. If
the 'i-PCB' Alarm input detects a voltage between
12-250VAC/DC, an alarm (Warning) condition is
generated. The values for this parameter are:
+V=! for an Alarm (Warning) condition is
o
generated if the 'ir-PCB' Alarm input
detects a voltage between 12-250Vac/dc
(default)
0V=! for an Alarm (Warning) condition is
o
generated if the 'ir-PCB' Alarm input
detects no voltage.
5. Scroll up (+)
to change the value for the Alarm condition
required for your application. Press the enter
button to confirm your selection.
All manuals and user guides at all-guides.com
or scroll down (-)
or scroll down (-)
or scroll down (-)
or scroll down (-)
6. The flashing cursor should be displayed
highlighting the Compressor Run-On Stop Time.
The Default setting for this parameter is 0 Sec.
This is the time that the compressor main motor
will continue to run when the compressor is
unloaded. The time is from the moment the
compressor unloads until the main motor stops
and the compressor enters a 'Standby' or 'Auto
Restart' condition. This setting is only applicable
to 'IRV-PCB' connectivity and is not displayed for
other connectivity options. The values for this
parameter are "0" to "999".
7. Scroll up (+)
to change the value to the time required. Press
the enter
You should be returned to the C02 home screen
and 'irv-PCB' should appear next to the 01-01
parameter.
8. Repeat this by scrolling up (+)
scrolling down (-)
to highlight the remaining compressors and set
the Compressor Connection type and the
Compressor Connection parameters for each of
the other compressors.
9. You should be returned to the C02 home screen
each time after completing the Compressor
Connection Setting and values just entered
should appear next to the 01 to 04 parameters
Once all values have been entered for all
compressors, you should be returned to the C02
home screen and all 'i-PCB' values entered
should appear next each compressor parameter.
10. After you have completed adjusting the settings
on the C02 screen press the escape
to return to the page selection screen.
16
or scroll down (-)
button to confirm your selection.
or
to move the cursor
button