9. After you have completed adjusting the settings
on the S01 screen press the escape
to return to the page selection screen.
COMPRESSOR CONNECTION
CONFIGURATION

C02 TAB SCREEN

1. After you have returned to the page selection
screen, scroll up (+)
until the C02 page is highlighted.
C02 Tab Screen
2. Press the enter
selection. The cursor should be flashing on line
01 01.
C02 Home Screen

COMPRESSOR CONNECTION METHOD

1. From the C02 home screen scroll up (+)
or scroll down (-)
highlight 01- 01 (Compressor 1 Connection
Settings).
All manuals and user guides at all-guides.com
button
or scroll down (-)
button to confirm your
to move the cursor to
Compressor Connection Settings
2. The default setting for this parameter is I-PCB.
This setting is used for the type, method of
connection, and the control functionality, of each
compressor connected to the X4I. Each air
compressor in the system is integrated with the
X4I using an interface module.
3. Press the enter
Compressor Connection setup screen for
compressor #1. The flashing cursor should be
displayed highlighting the I-PCB. The values for
this parameter are:
"IR-PCB" for Fixed speed, load/unload;
o
connected to X4I using 'ir-PCB' module
using 6-wire method.
"IRV-PCB" for Variable Speed; connected
o
to X4I using 'ir-PCB' module employing
the 7-wire 'V' terminal method.
"I-485" for Fixed speed, load/unload;
o
connected to X4I on Multi485 network.
"V-485" for Variable Capacity/Speed;
o
connected to X4I on Multi485 network.
NOTE: Quick Setup only requires the selection of Option
A or B. For information on Option C or D, please refer to
the Operator's Manual.

IR-PCB SETUP

1. Scroll up (+)
to change the value to IR-PCB. Press the enter
button to confirm your selection.
2. The flashing cursor should be displayed
highlighting the Compressor Start Sequence
Time. The Default setting for this parameter is
10 Sec. This is the time required to start the
motor and then load the compressor. The values
for this parameter are "0" to "60".
3. Scroll up (+)
to change the value to the time required. Press
the enter
15
button to display the
or scroll down (-)
or scroll down (-)
button to confirm your selection.