POWER FAILURE AUTO-RESTART
If the power failure auto-restart function is enabled, the
X4I will automatically start when power is restored after a
disruption or failure, if the X4I was in a 'started' state
when the power disruption or failure occurred.
NOTE: The Default setting for Power Failure Auto Restart
is ON.
NOTE: The X4I will not automatically restart if it was in a
stopped state when the power disruption or failure
occurred.
FAILURE MODE
If the X4I experiences a disruption to normal control, or
an X4I shutdown fault occurs, pressure regulation control
is automatically transferred back to each compressor.
The compressor(s) will continue to operate using the
pressure settings programmed or set in the individual
compressor controller(s).
RESET
To reset an X4I Alarm (Warning) or Shutdown condition,
press RESET. Compressor Alarm (Warning) conditions are
automatically reset when the condition has been resolved
and reset on the compressor. "Compressor Not
Available" (Shutdown, Trip) conditions are automatically
reset when the condition has been resolved and reset on
the compressor; and the compressor has been restarted.
All manuals and user guides at all-guides.com
10
COMPRESSOR IDENTIFICATION
Each compressor connected to the X41 will have a unique
assigned compressor identification number; starting at
compressor 1 and increasing sequentially to the number
of compressors connected to the unit.
Ingersoll Rand
psi
102
1
2
3
4
1
2
3
FAULT CODES
In the event of a unit or system "Fault", the X4I will
display a fault code. The fault code becomes an item in
the user operational display menu. If more than one
"active" fault occurs, each will be displayed as a separate
item in the operational user menu. Press UP or DOWN to
view all active fault codes or to view the normal status
display.
See the section on Fault Codes in the Operator's
Manual for more information.