Ferroli Connect CRP Manual De Instalacion Y Uso página 108

Tabla de contenido
Idiomas disponibles
  • ES

Idiomas disponibles

  • ESPAÑOL, página 39
While the minimum flow temperature is limited by the value set on the unit, the upper threshold of the curves is deter-
mined by the HEATING USER SET POINT parameter (MENU >> SETTINGS >> TECHNICAL >> ZONES MANAGER
>> (CHOOSE THE DESIRED ZONE) >> CLIMATIC CURVES >> HEATING >> USER SETPOINT).
If the USER SETPOINT value is greater than the maximum flow temperature set on the unit, then the
Note
curves will be limited to this latter value.
Example: curves with "USER SETPOINT" set at 60 °C, max. flow temperature set on the unit at 65 °C, min. flow
temperature set on the unit of 25 °C and offset of 30 °C.
80
70
[ a ]
65
[ b ]
60
50
40
30
[ c ]
25
20
25
20
15
In addition to the climatic curve and the OFFSET, the CRP allows the setting of parameter K, which will affect modu-
lation of the flow temperature as a function of the room temperature:
if the room temperature is between the set point - 2 °C and the set point + 0.1 °C, the flow temperature set point will
be equal to
Heating user setpoint – K*(T_amb + 2 -Tcomfort)
where T_amb is the room temperature and T_comfort is the desired temperature
PERMISSIBLE RANGES:
CLIMATIC
OFFSET
K
USER SETPOINT
108
EN
10
5
0
-5
A
fig. 80
0 – 10 (0 = Climatic not enabled)
20 °C – 40 °C
0 – 20
25 °C ÷ 65 °C
cod. 3542B380 - Rev 00 - 05/2022
[ a ] = Max. flow temperature set on the unit
[ b ] = USER SETPOINT
[ c ] = Min. flow temperature set on the unit
-10
-15
-20
Tabla de contenido
loading

Tabla de contenido