Problem
The display shows Not enough vacu-
um! Carry on?
The display shows A/C system leak-
age! Carry on?
The display shows Warning! Not
enough vacuum for injection!
The display shows Quantity too
large. Fill internal vessel!
The display shows Not enough UV.
Add!
The display shows Not enough oil.
Add!
The display shows Max. filling
time exceeded! Carry on?
The display shows External tank
empty or closed valve. Check!
The display shows Change the
equipment drier filter! Go on?
The display shows Change the vacu-
um pump oil! Go on?
The display shows Printer not in
line! Carry on?
The display shows Error 01
The display shows Error 02
The display shows Error 52
Possible cause
Message that appears during the vac-
uum process if the pressure in the air
conditioning system after 8 min is still
more than 50 mbar.
Message at the end of the vacuum
process. The air conditioning system
shows a vacuum loss of more than
120 mbar during the checking time.
Message that appears during the filling
phase if the vacuum in the air condi-
tioning system is insufficient to end the
process.
Message that appears during the
process input if there is not enough
refrigerant in the internal container to
complete the process.
This message appears during the fill-
ing process if there is not enough UV
additive in the container to finish the
process.
Message that appears during the filling
process if there is not enough fresh oil
in the container to finish the process.
Message that appears during the filling
process if the set amount of refrigerant
cannot be filled.
Message that appears at the start or
during the filling of the internal refriger-
ant container if the set refrigerant quan-
tity cannot be attained.
This message appears when you
switch on the A/C service unit.
This message appears when you
switch on the A/C service unit.
Message indicates a printer fault.
Refrigerant was added before draining
was completed.
The air conditioning system is leaking.
There is still refrigerant in the air condi-
tioning system.
No USB flash drive was found/recog-
nised.
Suggested remedy
Check the air conditioning system or
the connections between it and the A/C
service unit for leaks.
Check the air conditioning system or
the connections between it and the A/C
service unit for leaks.
Check the air conditioning system or
the connections between it and the A/C
service unit for leaks.
Fill the refrigerant container.
Fill the UV additive container.
Top up the fresh oil container with a
suitable oil type.
Check that A/C service unit's connec-
tions are not blocked.
Check if the external refrigerant con-
tainer still contains enough refrigerant
or if the valves of the external refriger-
ant container are open.
Change the internal filter as soon as
possible
(Changing the dryer filter
page 23). To skip this, press ENTER
for 3 seconds.
Change the vacuum pump oil as soon
as possible
(Changing the vacuum
pump oil
on page 25). To skip this,
press ENTER for 3 seconds.
Check if there is paper in the
printer.
Check if the printer is switched
on (yellow LED must be lit con-
stantly).
Check that the cover is closed
properly.
Repeat the draining procedure; do not
interrupt it this time.
Fix the leak.
Insert the USB flash drive.
Ensure that the USB flash flash
drive has been formatted with the
FAT32 file system.
English
on
29