2. In-Row Cooler Installation
2.3 Placement Clearance
Using its casters, install the In-Row Cooler beside a rack enclosure. Ensure the installation area has sufficient clearance for
both airflow and maintenance and repair. Refer to Figure 2-3: Installation Clearance Requirements below.
48 in.
(1200 mm)
39.4 in.
(1000 mm)
Figure 2-3: Installation Clearance Requirements
If installing the cooling unit at the end of a row, a minimum of 19 in. (460 mm) clearance is needed on the side for servicing.
Adjust the leveling feet to ensure the entire unit is level for proper condensate drainage.
Secure the unit directly to the adjacent rack enclosure using baying brackets. For installation next to Tripp Lite racks, use the
Z-shaped baying brackets included with the cooler. Refer to Protruded (left) and Flush (right) installation diagram below.
Figure 2-4: Protruded (left) and Flush (right) installation
6