1. Important Safety Information
Hazard to equipment or personnel
• All work must be performed only by qualified personnel.
Failure to observe this warning may result in death or serious injury.
Hazard of equipment falling over
• Use two or more persons at all times to move or turn this equipment.
• Always push, pull, or turn while facing the front and rear of this equipment. Never push pull, or turn while facing
the sides of this equipment.
• Slowly move this equipment across uneven surfaces or door thresholds.
• Lower leveling feet to floor when this equipment is at rest.
• Lower leveling feet and attach joining brackets to adjacent racks when this equipment is in final position.
Failure to observe this warning may result in serious injury or equipment damage.
Hazard to equipment or personnel
• Make sure no spare parts or tools are in the equipment before handling the equipment.
• Do not operate unit without the air filter. This may cause dust accumulation that can damage the unit.
Failure to observe this warning may result in serious injury or equipment damage.
Refrigerant high pressure and hazard to equipment
• This unit operates under high pressure. Observe proper safety precautions when operating or servicing the unit.
• The equipment is to be charged with R-410A refrigerant only.
• Copper pipe must support minimum 55 bar pressure.
Failure to observe this warning may result in serious injury or equipment damage.
The SRCOOLDXRW12 and SRCOOLDXRW25 In-Row Air Conditioning Systems are precision, split type, DX, air-cooled systems.
They require copper piping connections to bridge the In-Row Cooler (indoor) with the condenser (outdoor). No ductwork
or raised floor is required. As a result, these are dedicated cooling systems, meaning the design enables them to operate
independently of the building's HVAC/comfort cooling system.
The system requires charging with R-410A refrigerant.
Notes:
• These are cooling-only devices with no heating capability.
• In-Row Coolers shall be spaced properly to provide coverage across all rack enclosures. Ensure the total number and placement of all
coolers adheres to the redundancy model required as per customer design. Typical redundancy is n+1.
• Install the In-Row Cooler either on a solid surface or a raised floor. Ensure the floor is level.
• The In-Row Cooler design is for data centers and other cleanroom applications. It is not intended for harsh or dirty environments.