6. Startup and Commissioning
6.5 Commissioning
Each In-Row Cooler requires a minimum heat load for constant cooling operation. The total heat load for the room must be
greater than ~3kW (SRCOOLDXRW12) or ~7kW (SRCOOLDXRW25). If the total heat load is lower than the minimum, the
cooler will go into start/stop mode.