Learning Mode - Burkert 3004 Manual De Instalación Y Funcionamiento

Tabla de contenido
Idiomas disponibles

Idiomas disponibles

POSI-BBPR (GPS): electric connection
Power supply wiring
Ensure that the voltage indicated on the actuator ID label corresponds to the voltage supply.
Unscrew the left cable gland and insert the cable.
Remove 25mm of the cable sheath and strip each wire by 8mm.
Connect the wires to the terminal strip in accordance with the diagram p. 53.
Tighten the ATEX & IP68 cable gland (Ensure that it's well mounted to guaranty the proofness).
Setpoint and feedback wiring
Unscrew the right gland and pass the cable.
Connect the input signal between terminals 15 and 16. Terminal 15 is the negative polarity (-) and terminal 16 is the positive
polarity (+).
Connect the output signal between terminals 13 and 14. Terminal 13 is the positive polarity (+) and terminal 14 is the negative
polarity (-).
Tighten the ATEX & IP68 cable gland (Ensure that it's well mounted to guaranty the proofness).
Factory setting : by default, 4-20mA input and output signals with normal rotation sense.

Learning mode

Switch on the actuator
Press both OPEN and CLOSE buttons until the learning mode is selected, (APPR LED on).
Press CLOSE button. The valve operate into closed position.
When the valve is closed, press both CLOSE and MEM buttons during 2 seconds.
The APPR2 led blinks rapidly and then lights on. The closed position is stored.
Press OPEN button. The valve operate into open position.
When the valve is open, press both OPEN and MEM buttons during 2 seconds.
The APPR1 led blinks rapidly and then lights on. The closed position is stored
Exit the learning mode by simultaneously pressing the OPEN and CLOSE buttons to the POSI mode.
Thanks to remot3XApp (via Bluetooth
of power failure (BBPR function) as well as setpoint and feedback signal type (positioning function).
it's also possible to access to actuator parameters in real time, to schedule weekly tasks and to control it locally.
Be sure you connect the terminal 15 (-) before the terminal 16 (+)
The battery charge cycle is automatically managed by the electronic card since the first power up. A CTN in the battery
pack and a fuse on the electronic card are present to ensure safety in the event of a short circuit or excessively high tempe-
rature in the actuator .
Following a power failure, the BBPR unit will reset after 4 minutes.
52
®
connection), it's possible to set the Initial security position that the actuator will reach in case
EN
3004 • Rev. 2109/06 • 00806090