Description; Bbpr (Gs6) Models - Burkert 3004 Manual De Instalación Y Funcionamiento

Tabla de contenido
Idiomas disponibles

Idiomas disponibles

BBPR models (GS6)
Actuators with battery backup position recovery system (on-off wiring mandatory)
BBPR models integrate a battery pack monitored by an electronic board inside the actuator. Its function is to relay in
case of power supply failure on terminal PIN 1,2 and 3 of the actuator. The BBPR system can be set on different position
like normally open (NO) or normally closed (NC). It depends on the application.
The electronic board monitors the battery pack and check the status of battery (cycle load and failure)
If a battery failure is detected , a contact on PIN 65 and 66 switch off. It's possible to use this contact to be aware that
there is a failure on battery in the actuator without remove cover and plan the replacement.
BBPR option requires ON/OFF mode.
Loading electronic board
LED

DESCRIPTION

D19
L1
Actuator operating into opening
green
D18
L2
Actuator operating into closing
red
Battery status :
ACT
Slow blinking (1s) : battery charged.
L3
green
Rapid blinking (0.5s) : battery charging
Error detected:
Timestamp memory empty/scheduler selected
ERROR
Clock failure
L4
red
Excessive temperature
Excessive torque
HORO
L5
Orange Weekly scheduler functioning mode
MANU
L6
Orange manual / Bluetooth
WIRE
L7
Orange Electric wiring mode
CONNECTEUR
C1
17 (-) · 18 (+)
C2
F (+) · F (-) · T (+)
C3
A · B · C
1)
C4
D3 · D4
1)
C5
65 · 66
C6
A · 0 · B
®
J1
Bluetooth
activation jumper
1) The auxiliary cables must be connected to inside installation only
The factory default configuration is "normally closed"
Following a power failure, the BBPR unit will reset after 4 minutes
II 2 G D Ex db IIB T6 Gb Ex tb IIIC T80 °C Db LCIE 07 ATEX 6078X / LCIE 22.0001X
Ambient temperature: -10 °C to +40 °C
48
®
functioning mode
DESCRIPTION
power supply connector
Battery unit connector
Motor connector
Failure feedback connector
Charging feedback connector
RS485 connector
L4
J1
L3
C3
C2
C1
Battery voltage
Battery capacity
Charging current
initial battery charge duration
Charging status feedback relay
(65/66)
Failure feedback relay (D3/D4)
Temperature
3004 • Rev. 2109/06 • 00806090
EN
L6
C6
L5
L7
L1
C4
L2
C5
24 V DC
600 mAh
180 mA
3,5 h
24 V DC - 1 A max
24 V DC - 3 A max
-10 °C to +40 °C
Tabla de contenido
loading

Tabla de contenido