Always test detectors after installation.
Note: Please note that all models in the 700 Series are polarity
insensitive. Polarity must be observed when using remote
indicators.
Maintenance
To remove a locked detector:
1.
Insert a small screwdriver into the locking tab
slot (Figure 2).
2.
Press in and rotate the detector anticlockwise.
All detectors ship with a plastic dust cover. Smoke detectors
will not work with the dust cover in place. It must be removed
when installation is completed, before testing.
To replace the optical chamber:
1.
Remove the detector head from the mounting base.
2.
Remove the detector cover by inserting a screwdriver and
lifting as shown in Figure 3.
3.
Remove the used optical chamber from the detector
(Figure 4) and insert the replacement optical chamber.
4.
Replace the detector cover by placing onto detector head
and pushing down until it clicks into place. Install the
detector back into the mounting base.
5.
Test the detector according to local regulations and verify
that it signals an alarm at the control panel.
To clean the optical chamber, follow the above instructions for
removal and use compressed air to clear the dust.
Caution:
After replacing or cleaning the optical chamber,
check for sensitivity with the sensitivity level test described
below.
Testing
For in-depth sensitivity testing, see sensitivity level test mode
in Table 2 below. The test is initiated by holding a magnet to
the integral reed switch, marked by the word TEST on the
detector housing. The test results are indicated by the number
of times the LED flashes, as shown. Reset the detector once
testing is completed.
Table 2: Sensitivity level test mode
Obscuration [1]
Flashes
1
> 9
2
8.4
3
7.2
4
6.1
5
4.9
6
3.8
7
2 / 28
Indication
Unserviceable hardware fault is
detected.
Reset detector and re-run test. If
indication remains the same, replace
detector.
The detector is not sensitive enough.
Clean per instructions. Check to
make sure the optical block cover is
snapped down completely.
The detector is within the sensitivity
limits.
None.
Obscuration [1]
Flashes
2.6
8
< 2
9
[1] Approximate based on (%/m) photo detector
Specifications
Operating voltage
8.5 to 33 VDC
Current
Standby
100 µA
Alarm
15 to 60 mA
Relay contact
2 A at 30 VDC
1 A at 120 VAC
IP rating
IP43
DB702, DB702U
Compatible mounting
bases
Relative humidity
0 to 95% noncondensing
Temperature
−10 to 60ºC
Operating
−10 to 70ºC
Storage
Colour
White
Dimensions (Ø × H)
100 × 50 mm
Weight
DP721I
112 g
DP721R, DP721RT
115 g
DP721T
109 g
DT713-5
84 g
DT713-5R
87 g
DT713-7
85 g

Regulatory information

This section provides a summary on the declared performance
according to the Construction Products Regulation
(EU) 305/2011 and Delegated Regulations (EU) 157/2014 and
(EU) 574/2014.
For detailed information, see the product Declaration of
Performance (available at
https://www.utcfssecurityproducts.eu/).
EU compliance
Certification body
1134
Manufacturer
United Technologies Safety Systems,
80 Changjiang East Road, QETDZ,
Qinhuangdao, Hebei, China 066004.
Authorized EU manufacturing
representative:
UTC Fire & Security B.V. Kelvinstraat 7,
6003 DH Weert, Netherlands.
Year of first CE marking
05
Declaration of
Performance number
DP721I, DP721R
360-4227-0399
DT713-5, DT713-5R,
360-4227-0599
DT713-7
360-4227-0599
DP721RT, DP721T
360-4227-0799
P/N 10-4226-501-1C70-08 • ISS 11NOV16
Indication
The detector is too sensitive.
Clean per instructions