700 Series Conventional Point Detector
Installation Sheet
EN CS DA DE ES
FI
1
3
EN: Installation Sheet
Description
The 700 Series Conventional Point Detectors are compatible
with with DB702 and DB702U mounting bases.
Table 1: 700 Series Conventional Point Detectors
Model
Detector type
DP721I
Optical Smoke Detector with Remote Indicator Output
DP721R
Optical Smoke Detector with Relay Output
DP721RT
Optical/Heat Multi Detector with Relay Output
DP721T
Optical/Heat Multi Detector with Remote Indicator Output
DT713-5
Heat Detector, 57° C fixed and rate of rise heat detector
DT713-5R
Heat Detector, 57° C fixed and rate of rise heat detector
with relay output
DT713-7
Heat Detector, 70°C fixed and rate of rise heat detector
© 2016 UTC Fire & Security. All rights reserved.
FR HU
IT
NL NO PL PT RO SV TR
2
4
Installation
Caution:
For general guidelines on system planning, design,
installation, commissioning, use and maintenance, refer to
CEN/TS 54-14 and to local regulations.
To install a detector:
1.
Insert the detector head into the mounting base and rotate
it clockwise until it clicks into place.
The detector may be locked into the mounting base if required.
To do this remove the locking tab on the detector before
installation (Figure 1).
Every 700 Series base features a continuity link between LINE
IN (1) and LINE OUT (2) terminals of the conventional detector
circuit. The base is supplied with the link in closed position.
The link is enabled by default allowing you to check the zone
wiring using only the bases. The link will automatically
disconnect when a detector is inserted, allowing the panel to
generate a fault message when the detector is removed.
1 / 28
P/N 10-4226-501-1C70-08 • ISS 11NOV16
Tabla de contenido
loading

Resumen de contenidos para Aritech 700 Serie

  • Página 8: Especificaciones

    protector contra el polvo puesto. Hay que quitarlo una vez Especificaciones completada la instalación, antes de realizar la prueba. Tensión de De 8,5 a 33 VCC Para sustituir la cámara óptica: funcionamiento Corriente Extraiga la cabeza del detector del zócalo de montaje. Reposo 100 µA Retire el protector del detector insertando un...
  • Página 26 26 / 28 P/N 10-4226-501-1C70-08 • ISS 11NOV16...
  • Página 27 P/N 10-4226-501-1C70-08 • ISS 11NOV16 27 / 28...
  • Página 28 28 / 28 P/N 10-4226-501-1C70-08 • ISS 11NOV16...

Tabla de contenido