Electric Connections; General Connecting Requirements - HYDROO VDROO Serie Manual De Instrucciones De Instalación Y Operación

Tabla de contenido
Idiomas disponibles

Idiomas disponibles

Flange
DN
Model
Fx
[mm]
DN25
VF, VX, VN 1
780
DN25
VF, VX, VN 3
780
DN32
VF, VX, VN 5
780
DN40
VF, VX, VN 10
1100
DN50
VF, VX, VN 15
1500
DN50
VF, VX, VN 20
1500
DN65
VF, VX, VN, VD 32
1875
DN80
VF, VX, VN, VD 42
2250
DN100
VF, VX, VN, VD 65
3000
DN100
VF, VX, VN, VD 85
3000
DN125
VF, VX, VN, VD 120
3000
DN125
VF, VX, VN, VD 150
3000
DN150
VF, VX, VN, VD 200
3000
78
Force [N]
Torque [N·m]
Fy
Fz
Mx
My
760
1170
1220
820
760
1170
1220
820
760
1170
1220
820
1000
1250
1300
900
1350
1650
1400
1000
1350
1650
1400
1000
1700
2075
1500
1075
2050
2500
1600
1150
2700
3350
1750
1250
2700
3350
1750
1250
2700
3350
1750
1250
2700
3350
1750
1250
2700
3350
1750
1250

6. ELECTRIC CONNECTIONS

Mz
970
970
970
1050
1150
1150
1225
1300
1450
1450
1450
1450
1450
The power voltage and frequency is specified on the motor's specifications plate.
Make sure that the motor is suitable for the power supply and that the motor terminal
connection is correct.
6.1. General connection requirements
Verify if the following requirements are met:
· Electric wires are protected against high temperature, vibration and impact.
· The power source is fitted with the following:
ATTENTION:
· Electric connections must be carried out by a qualified electrician
according to local regulations.
· The user must determine if it is necessary to install an emergency stop
switch.
· Pumping equipment must be fitted with all the safety devices required
by the directive EN-60204-1, as well as all those regulations applicable
in the country where the pump is to be installed..
DANGER:
Before removing the electric connections box and before removing/
dismantling the pump, make sure it has been unplugged from the mains
and that it cannot be accidentally switched on.
- Short-circuit protection (circuit breaker)
- High sensitivity residual current device (30 mA) to offer additional
protection against electric shock.
- Main switch with a contact surface of at least 3 mm.