Display Menu - Schneider Altivar 28 Manual De Usario

Variadores de velocidadpara motores asíncronos
Tabla de contenido
Idiomas disponibles
  • ES

Idiomas disponibles

Settings

Display menu

S S S S U U U U P P P P -
fault, speed controller software version and access code)
The display chosen is saved by :
- Pressing the ENT key once: the choice is temporary, it will be cleared at the next power up
- Pressing the ENT key twice : the choice is permanent. The second press on ENT exits the SUP- menu
The following parameters can be accessed, with the speed controller stopped or running.
Code
Parameter
- - - - F F F F r r r r H H H H Display the frequency reference
- - - - r r r r F F F F r r r r Display the output frequency applied to the motor
- - - - S S S S P P P P d d d d Display the value calculated by the speed controller (rFr x SdS)
- - - - L L L L C C C C r r r r Display the motor current
- - - - O O O O P P P P r r r r Display the power supplied by the motor, estimated by the speed controller
100 % corresponds to the nominal speed controller power
- - - - U U U U L L L L n n n n Display the line voltage
- - - - t t t t H H H H r r r r Display the motor thermal state : 100% corresponds to the nominal thermal state
Above 118%, the speed controller triggers an OLF fault (motor overload)
- - - - t t t t H H H H d d d d Display the speed controller thermal state : 100% corresponds to the nominal thermal state
Above 118%, the speed controller triggers an OHF fault (drive overheated LED)
It can be reset below 70%
- - - - L L L L F F F F t t t t View the last fault which appeared. If there has been no fault, the display shows : noF
- - - - C C C C P P P P U U U U Speed controller software version
- - - - C C C C O O O O d d d d Access code : 0 to 9999. Value 0 (factory setting) does not prevent access. All other values lock access
to the SEt-, drC- and I-O- menus
To lock access to the speed controller, the code can be incremented using (
• Do not forget to make a note of the code, as once it has been saved, it is no longer
displayed
To access the menus on a speed controller which is locked by a code, the code can be
incremented using (
• If the correct access code is displayed, it flashes, and code 0 can then be configured in order
to access the menus
• If an incorrect code is displayed, the speed controller returns to the initial display (rdY)
(choice of parameter to be displayed during operation, view the last
) and confirmed with (ENT) :
Unit
Hz
Hz
A
%
V
%
%
) then saved using (ENT)
90