Setup - Preliminary Recommendations
Manual starting
Important: In factory settings mode, on power-up or a manual fault reset or after a stop command, the
motor can only be powered once the "forward", "reverse" and "DC injection stop" commands have been
reset. If they have not been reset, the drive will display "rdY" but will not start. If the automatic restart
function is configured (parameter Atr in the drC menu see page 85), these commands are taken into
account without a reset being necessary.
Test on a low power motor or without a motor
In factory settings mode, motor phase loss detection is active (OPL = YES). To check the drive in a test
or maintenance environment without having to switch to a motor with the same rating as the drive
(particularly useful in the case of high power drives), deactivate motor phase loss detection (OPL = no).