Ionization Current - Ecoflam BLU 7000.1 PR/MD Manual De Instrucciones

Tabla de contenido
Idiomas disponibles

Idiomas disponibles

The ionization current is checked by inserting a
microammeter with an end of scale of 50 µA (d.c.)
in series with the ionization probe.
A faulty position of the electrode can lead to a
reduction in the ionization current and cause a
safety cut-out of the burner due to a flame detec-
tion failure. In this case, check the position of the
electrode, its electric connection and the earthing
of the burner. The ionization current is normally >
20 µA.
REMOVING THE BLAST TUBE
DESCRIPTION OF THE CONTROL PANEL OF THE BURNER
F
A
B
C
D
E

IONIZATION CURRENT

A-
B-
AUTO
I
C-
0
0
D-
E -
F -
LB1215 BLU 7000.1 - 12000.1 PR / MD B
Microamperometro
Microammeter
fondo scala 50 µA
50 µA end of scale
main switch I / O
fuse
selector :
0
= operating elements locked in an
intermediate position
= operation on maximum capacity
= operation on minimum capacity
AUTO = automatic operation
thermal relaylock-out lamp
working lamp
reset key
pag.19
min. 6 µA
LANDIS LFL1.622
FIRING HEAD
DISASSEMBLY
24
Tabla de contenido
loading

Este manual también es adecuado para:

Blu 8000.1 pr/mdBlu 10000.1 pr/mdBlu 12000.1 pr/md

Tabla de contenido