CXRT, GT
5. Service intervals
Table 5.1 GT-1 fan maintenance plan.
Fan
Motor
Motor bearings
Flexible connection duct
Table 5.2 GT-3 and GT-5 maintenance plan.
Belt
Bearings
Fan
Motor
Flexible connection duct
6. Trouble shooting
1. No air comes out of the fan
– Check the functioning of the motor, heat shield
and the fuses
– Check that the belts are not broken
2. Pressure rise and air flow too low
– Check the direction of rotation and the speed of
the fan
– If there is an undesirable duct bend in close proximity
to the outlet opening, then the connection losses
may be greater than expected -> check the ducting
and use baffle plates, if necessary
3. Fan vibrates
– Check the anti-vibration mountings
– Check that the impeller is not dirty
– Check the bearings
– Check the alignment of the belt drive pulleys
– Check that the bearings, hub and pulleys are properly
secured
4. Abnormal noise from bearings
– See Section 4.7 "Checking the bearings"
5. Repeated bearing damage
– Excessive bearing loads (i.e. belts have been
tightened too much)
– Poor or inadequate lubrication
– Impurities have entered the bearing
14
Service action
Cleaning of casing and impeller
Cleaning
Listening to noises
Monitoring temperature
Checking
Soundness and tightness
Service action
Visual inspection
Tensioning
Listening to noises
Monitoring temperature
Checking
Cleaning (with housing)
Cleaning of casing and impeller
Cleaning
Soundness and tightness
3 months
6 months
9 months
X
X
X
X
3 months
6 months
9 months
X
X
X
X
X
X
X
X
Service and repair
12 months
24 months
X
X
X
X
X
X
X
X
X
X
X
X
12 months
24 months
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X