Keep your TR performing at its best by cleaning it as described
below:
www.renewaire.com
RISK OF ELECTRIC SHOCK OR INJURY.
• Before servicing or cleaning the unit, unplug the
unit line cord.
• Make sure unit is not running before opening its
door. Blower wheels are sharp and can cut.
• Do not disable the interlock switch: it is there for
your safety.
Service filters regularly:
Service filters every three months when the unit is in regular use
or as needed to keep them reasonably clean.
1.
Release cam latches and carefully swing access door open.
Remove the door by sliding to one side.
2.
Remove filter clips and pull out the filters.
3.
Vacuum core and filters with a hose attachment.
4.
Re-install filters and filter clips, (see above).
5.
Re-install door, and fasten cam latches.
NOTE: The filters should be replaced after they have been cleaned
several times. The primary contact for replacement filters for
your S&P unit is the installing contractor. As an alternative, you
may wish to produce your own filters.
TR130_200_300
132100_003
Maintenance Requirements
(800) 627- 4499
Due to continuing product development, specifications are subject to change without notice.
Service Parts
Please follow these instructions:
Filters may be cut from a sheet or roll of ¾" - 1" firm, spun
polyester filter "hog hair" media or material, similar to the
existing filter in the residential unit.
The size of each filter (2 required per unit) are as follows:
TR130
TR200/TR300
Call your HVAC contractor or S&P for further information.
NOTE: Filters must be used or the face of the energy exchange
core will become blocked by dust. The filters supplied in the
unit are usually able to keep the energy exchange core clear
for many months. Finer filters can be used but must be cleaned
more often.
Clean the face of the energy exchange core yearly:
1.
Remove the filters (see above).
2.
Vacuum the exposed faces of the energy exchange core with
a soft brush attachment.
3.
After servicing the filters, re-install them (see above).
4.
Vacuum out dust from the rest of the unit case.
Dust collects only on the entering faces of the energy exchange
core. The interior of the energy exchange core stays clean even
if the core faces are dust covered.
The blower/motor package needs no lubrication:
Vacuum clean the blower wheels at the same time you clean
the face of the energy exchange core.
10 1/2" x 10 1/2"
10 1/2" x 21 3/4"
Revised 9/2018
© 2018 S&P
Page 11