Tripp-Lite SmartOnline S3MX Manual Del Propietário página 58

Ocultar thumbs Ver también para SmartOnline S3MX:
Tabla de contenido
Idiomas disponibles
  • ES

Idiomas disponibles

  • ESPAÑOL, página 71
7. UPS Operation
Step 4
Turn OFF the Q3 Output breaker.
Step 5
Single input model:
Turn OFF the Q1 Input 1 breaker.
Dual input models (Optional):
Turn OFF the Q1 Input breaker and Q2 Input breaker.
Step 6
The UPS will enter Shutdown Mode and will slowly de-energise. After the UPS powers off, turn OFF the battery breaker
(external battery cabinet).
Step 7
The critical load is now supported in Maintenance Bypass Mode.
Q3
Output
S3M100KX/S3M100KXD
S3M120KX/S3M120KXD
(100 kVA/200 kVA) Models
Q1
Input 1
S3M100KX
S3M120KX
(100 kVA/200 kVA) Models
Q1
Input 1
Q2
Input 2
S3M100KXD
S3M120KXD
(100 kVA/200 kVA) Models
Turn OFF the Q3 Output breaker.
S3M160KX/S3M160KXD
S3M200KX/S3M200KXD
(160 kVA/200 kVA) Models
Single input model:
Turn OFF the Q1 Output breaker.
(160 kVA/200 kVA) Models
Dual input models (Optional):
Turn OFF the Q1 Input breaker, Q2 Input breaker.
(160 kVA/200 kVA) Models
58
Q3
Output
Q1
Input 1
S3M160KX
S3M200KX
Q1
Input 1
Q2
Input 2
S3M160KXD
S3M200KXD
Tabla de contenido

Solución de problemas

loading

Tabla de contenido