English
Control laws
Control lows in Mode 2
Sensor 4-20 mA
Between 0 and 4 mA it is assumed that the
cable is disconnected.
100%
0
External set value in Mode 2
Setpoint 0-20 mA
Area in which the frequency converter stops.
100%
10%
0
2
External control of the frequency in Mode 3
External signal 0-20 mA
Area in which the frequency converter stops.
100%
40%
0
2
36
4
20
Input current level (mA)
20
Input current level (mA)
20
Input current level (mA)
Sensor 0-10 V
100%
0
Input voltage (V)
Setpoint 0-10 V
Area in which the frequency converter stops.
100%
10%
0
1
Input voltage (V)
External signal 0-10 V
Area in which the frequency converter stops.
100%
40%
0
1
Input voltage (V)
10
10
10