BTL7-A/C/E/G5_ _-M_ _ _ _-B/Z-DEX_-K_ _/KA_ _
Micropulse Transducer - Rod Style
6
Calibration procedure (continued)
6.3

Calibration procedure overview

6.3.1

Teach-in

The factory-set null point and end point are replaced by a
new null point and end point. The null point and end point
can be set separately, the output gradient changes.
The detailed procedure for teach-in is described
on page 18.
Steps
► Move magnet to the new null position.
► Read new null point by activating the programming
inputs.
⇒ The current end point remains the same.
New null point
Fig. 6-2:
Reading new null point
16
english
► Move magnet to the new end position.
► Read new end point by activating the programming
inputs.
⇒ The current null point remains the same.
Fig. 6-3:
Reading new end point
Before
Only with BTL7-C/E...:
After
► The gradient of the current output can be inverted by
activating the programming inputs.
⇒ For example, a rising output gradient is changed to
a falling gradient. The voltage outputs are not
inverted.
Ignition protection "d"
Flameproof enclosure
Before
After
New end point