Power Cables; Cable Sizes; Internal Battery Installation - Model Bp240V09-Nib - Tripp-Lite BP240V09 Manual Del Usuario

Tabla de contenido
Idiomas disponibles

Idiomas disponibles

5. Installation

5.3 Power Cables

The cable design shall comply with the voltages and currents provided in this section, and in accordance with local electrical codes.
WARNING!
Typical battery performance data reflects an operating temperature between 59°F to 77°F (20°C to 25°C).
Operating the UPS above this range will reduce the battery life, while operating the UPS below this range
will reduce battery capacity.

5.3.1 Cable Sizes

Battery Cabinet
Models
BP240V09,
BP240V09K,
BP240V09-NIB
BP240V09,
BP240V09K,
BP240V09-NIB
BP240V40L,
BP240V40L-NIB

5.4 Internal Battery Installation - Model BP240V09-NIB

The battery box includes built-in battery cables, breaker, fuses and terminals and can holds 80 units of 12V 9Ah batteries, with
output voltage of ±120V by battery connection. Four groups of batteries are connected in parallel for use, and consist
of BAT+, N, BAT-.
Recommended
UPS Size
DC Cable AWG
10kVA
6 AWG
Max 6 AWG
15-20kVA
2 x 6 AWG
Max 6 AWG
25kVA
1/0 AWG
30kVA
1/0 AWG
10kVA
6 AWG
15-20kVA
2 x 6 AWG
25kVA
1/0 AWG
30kVA
1/0 AWG
50kVA
2/0 AWG
Figure 5-1: Models BP240V09 / BP240V09K / BP240V09-NIB
Recommended Ground
Cable AWG
6 AWG
Max 2 AWG (35mm
2 x 6 AWG
Max 2 AWG (35mm
2 AWG
1/0 AWG
6 AWG
2 x 6 AWG
2 AWG
1/0 AWG
2/0 AWG
22
Recommended
Cable Torque
Anderson Connector
)
(No Torque Parameter)
2
0kgf.com / 0N*m
)
2
450kgf.cm/
44N•m
450kgf.cm/
44N•m
Tabla de contenido
loading