6. Operation and Configuration of S3M UPS Models
and Battery Cabinets

6.2.3 Battery Setup

Click Battery Setup
6.2.4 Configuring the S3M10-20K UPS and Optimizing Charging of the
BP240V09/BP240V09K, BP240V40 and BP240V40L Battery Cabinets
Step 1: Setting the Battery Group
The Battery Group is Quantity 1 for every set of 20 batteries that are in and/or connected to the UPS model. For example,
UPS model S3M20K3B has 60 internal batteries and is Battery Group 3. However, to connect a BP240V09 cabinet with
80 internal batteries to the S3M20K3B, the S3M20K3B UPS must be configured to a Battery Group 7 (seven sets of 20
batteries). Obtain the Battery Group number based on the specific S3M UPS and Battery Cabinet models combination from
the chart under Section 6.4.
The value can be 1 to 8. The default value is 1 for S3M UPS models without internal batteries.
Step 2: Setting the Battery Number
The battery number must remain at 20 for all S3M10-100K UPS models when connected to Tripp Lite external battery
cabinets designed for the S3M-Series UPS Series.